– 22 –

EN

9

Test run

„

Before test run

Check valve of the refrigerant pipe of the outdoor unit is “OPEN”.
• Using 500 V-megger, check there is 1 M

Ω

 or more between the terminal block of the power supply and the earth. If the value 

is below 1 M

Ω

, do not operate the air conditioner.

WARNING

• In order to protect the compressor, keep the power ON for a period of 12 hours or more before starting the air conditioner.

„

How to perform a test run

In case of test run on the wired remote controller
Check the operation of the air conditioner in usual operation by the wired remote controller.
For the procedure of the operation, refer to the attached Owner’s Manual.
For a case of using a wireless remote controller, refer to the Installation Manual of the indoor unit.
A forced test run is available in the following procedure under condition that the thermostat-OFF in the room.
In a forced test run, the test run is cleared after operation for 60 minutes and then returns to the usual operation in order to 
prevent a serial operation.

NOTE

Do not use the forced test run for cases other than the test 
run because it applies an excessive load to the air 
conditioner.

In case of wired remote controller

1, 5

3

2, 4 

TEMP.

ON / OFF

SET

TIME

TEST

FILTER

RESET

CL

SAVE

SWING/FIX

VENT

UNIT LOUVER

E

D

O

M

T

E

S

 

R

E

M

I

T

FAN

Procedure

Operation

1

When pushing 

 button for 4 seconds or more, [TEST] is displayed

on the display part and the mode changes to test run mode.
([TEST] is displayed on the display part during test run.)

2

Push  

button.

3

Using 

 button, change the operation mode to [COOL] or [HEAT].

• Do not drive the air conditioner with a mode other than [COOL] or [HEAT].
• The temperature cannot be adjusted during test run.
• An error is detected as usual.

4

After the test run has finished, push 

 button to stop the operation.

(Display is same to that in procedure 

1

.)

5

Push 

 button to clear the test run mode.

([TEST] in the display part disappears and the status changes to the usual 
stop status.)

TEST

TEST

ON / OFF

MODE

ON / OFF

TEST

„

In case of test run on the interface P.C. board of the outdoor unit

This air conditioner has a function which executes a test run by operation of the switches on the interface P.C. board of the 
outdoor unit.
This function is classified into “Individual test run” which performs a test run individually in each indoor unit and “Collective test 
run” which performs a test run for all the connected indoor units.

[Individual test run]

[Collective test run]

Procedure

Operation

7-segment display

Start
operation

1

Set operation mode on wired remote controller of the indoor 
unit which is operated with test mode to [COOL] or [HEAT]. 
(When it is not set up, operate the air conditioner with the 
current operation mode.)

[A]

[U1]

[B]

[         ]

2

Set the rotary switch SW01 on the interface P.C. board of the 
outdoor unit to [16], and match SW02 and SW03 to the 
address of the indoor unit to be operated with test mode.

[A]

[         ]

Address display of the 

corresponding indoor unit

[B]

[         ]

3

Push SW04 for 10 seconds or more.
• Operation mode changes to the operation mode of wired 

remote controller of the corresponding indoor unit.

• Temperature cannot be adjusted during “Test run”.
• Error is detected as usual.
• Test run is not performed 3 minutes after power was turned 

on or operation has stopped.

[A]

[         ]

Address display of the 

corresponding indoor unit

[B]

[         ]

[FF] is displayed 

for 5 seconds.

Stop
operation

1

Return the rotary switches on the interface P.C. board of the
outdoor unit, SW01 = [1], SW02 = [1], SW03 = [1].

[A]

[U1]

[B]

[         ]

Procedure

Operation

7-segment display

Start
operation

1

Set the rotary switches of interface P.C. board of the outdoor unit; 
All cooling operation: SW01 = [2], SW02 = [5], SW03 = [1] 
All heating operation: SW01 = [2], SW02 = [6], SW03 = [1]

[A]

[C      ]
[H      ]

[B]

[         ]
[         ]

2

Push SW04 for 2 seconds or more.
• Temperature cannot be adjusted during “Test run”.
• Error is detected as usual.
• Test run is not performed 3 minutes after power was turned on or 

operation has stopped.

[A]

[C      ]
[H      ]

[B]

[  –C  ]
[  –H  ]

Stop
operation

1

Return the rotary switches on the interface P.C. board of the outdoor 
unit, SW01 = [1], SW02 = [1], SW03 = [1].

[A]

[U1]

[B]

[         ]

SW04 SW05 SW15

D600 D601 D602 D603 D604

SW03

1

SW02

1

SW01

1

SW06

1

ON

2 3 4

SW07

1

ON

ON

ON

ON

2 3 4

SW09

SW08

1

1

2 3 4

SW10

1 2 3 4

SW04 SW05 SW15

D600 D601 D602 D603 D604

SW03

1

SW02

1

SW01

1

Interface P.C. board

Push switch

7-segment 
display [A]

Push switch

Rotary switch

7-segment 
display [B]

43-EN

44-EN

Содержание MAP0601HT2DZG

Страница 1: ...01HT MCY MAP0601HT MCY MAP0401HTZ MCY MAP0501HTZ MCY MAP0601HTZ MCY MAP0401HTZG MCY MAP0501HTZG MCY MAP0601HTZG For commercial use Installation Manual English MCY MAP0401HT2D MCY MAP0501HT2D MCY MAP0601HT2D MCY MAP0401HT2DZ MCY MAP0501HT2DZ MCY MAP0601HT2DZ MCY MAP0401HT2DZG MCY MAP0501HT2DZG MCY MAP0601HT2DZG ...

Страница 2: ...matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work The qualified installer who is allowed to do the refrigerant handling and piping work involved in installation re...

Страница 3: ... undertake work Wear protective gloves and safety work clothing during installation servicing and removal Do not touch the aluminium fin of the outdoor unit You may injure yourself if you do so If the fin must be touched for some reason first put on protective gloves and safety work clothing and then proceed Do not climb onto or place objects on top of the outdoor unit You may fall or the objects ...

Страница 4: ...are closed and set the circuit breaker to the ON position You may receive an electric shock if the power is turned on without first conducting these checks When you have noticed that some kind of trouble such as when an error display has appeared there is a smell of burning abnormal sounds are heard the air conditioner fails to cool or heat or water is leaking has occurred in the air conditioner d...

Страница 5: ...rigerant Accordingly exclusive tools are required for the new refrigerant R410A as shown below For connecting pipes use new and clean piping materials so that water or dust does not enter Required tools and cautions on handling It is necessary to prepare the tools and parts for installation as described below The tools and parts which will be newly prepared in the following items should be restric...

Страница 6: ...s feet There must be sufficient space for carrying in the unit A place where the drain water does not make any problem CAUTION 1 Install the outdoor unit at a place where discharge air is not blocked 2 When an outdoor unit is installed in a place that is always exposed to a strong wind like a coast or on a high story of a building secure a normal fan operation by using a duct or a wind shield 3 Wh...

Страница 7: ...t 3 Evacuate the air in the connecting pipes using VACUUM PUMP 4 Check gas leak at connected points For reference If a heating operation would be continuously performed for a long time under the condition that the outdoor temperature is 0 C or lower draining of defrosted water may be difficult due to freezing of the bottom plate resulting in a trouble of the cabinet or fan It is recommended to pro...

Страница 8: ...5 1 5 to 2 0 1 0 to 1 5 15 9 2 0 to 2 5 1 5 to 2 0 A 0 0 4 B Tightening of connecting part Unit N m Align the centers of the connecting pipes and tighten the flare nut strong as far as possible with your fingers Then fix the nut with a spanner and tighten it with torque wrench as shown in the figure As shown in the figure be sure to use a double spanner to loosen or tighten the flare nut of the va...

Страница 9: ...ecided at each capacity rank The maximum No of connectable indoor unit and the total value of capacity codes of the indoor units are also decided Connected section External size Internal size Standard outer dia of connected copper pipe Connected section Min thickness of coupling External size Internal size Min depth of insertion Oval value Standard outer dia Allowable difference C F K G 6 35 6 35 ...

Страница 10: ...lection of refrigerant piping for quiet place with PMV Kit No Piping parts Name Selection of pipe size Outdoor unit È 1st branching section Main pipe Size of main pipe Branching section È Branching section Branching pipe Pipe size between branching sections If the total capacity code value of indoor units exceeds that of the outdoor units apply the capacity code of outdoor units Branching section ...

Страница 11: ...from 1st branch to be named A NOTE Do not connect two or more indoor units to one PMV Kit Arrange one indoor unit and one PMV Kit set to 1 by 1 Allowable value Pipes Piping Length Total extension of pipe Liquid pipe real length 150 m L1 L2 L3 L4 a b c d e f g h I j k l m n Furthest piping length L 1 Real length 65 m L1 L3 L4 g n Equivalent length 80 m Max equivalent length of main pipe 50 m L1 Equ...

Страница 12: ...r the air purge at installation time Discharge of air in connecting pipes use Vacuum pump method from viewpoint of the protection of the earths environment For protection of the earth environment do not discharge the refrigerant gas in the air Using a vacuum pump eliminate the remaining air nitrogen gas etc in the unit If gas remains performance and reliability of the unit may be reduced After the...

Страница 13: ...on The refrigerant amount at shipment is indicated on the unit name plate Additional refrigerant charge R kg amount at site Real length of liquid pipe Additional refrigerant charge amount per liquid pipe 1m Table 1 Compensation by outdoor HP Table 2 Table 1 Table 2 L1 Ø9 5 10 m L2 Ø9 5 10 m L3 Ø9 5 5 m a Ø9 5 3 m Ø6 4 3 m c Ø6 4 4 m d Ø6 4 5 m NOTE If the additional refrigerant amount indicates a ...

Страница 14: ...upply capacity or inappropriate installation may cause a fire When connecting the installation wiring be sure that all fixing terminal are securely fixed Ensure earthling practice is correctly performed Grounding is necessary if earthling practice is incomplete an electric shock maybe caused CAUTION The installation fuse must be used for the power supply line of this outdoor unit Incorrect incompl...

Страница 15: ...arth leakage breaker Outdoor unit power supply N L 10 L N 10 50 90 Power cable Earth wire Power cable Terminal block Stripping length power cable Protective bush Accessory Cord clamp For Indoor unit power supply The outdoor unit has a separate power supply NOTE Power supply cord specification Cable 3 core 2 5 mm inconformity with Design 60245 IEC57 The connecting length indicated in the table repr...

Страница 16: ... 2 No 3 No 4 No 7 No 8 Connect each wire for controlling as shown below Wire specification quantity size of crossover wiring and remote controller wiring 1 The crossover wiring and central control wiring use 2 core non polarity transmission wires Use 2 core shield wires to prevent noise trouble In this case close connect the end of shield wires and perform the functional grounding for the end of t...

Страница 17: ...rth Earth Earth Earth Earth Option Outdoor power supply MCY MAP HT 1N 50 Hz 220 V 240 V MCY MAP HT2D 1N 60 Hz 220 V Central remote controller power supply 1N 50 Hz 220 V 240 V 1N 60 Hz 220 V Outdoor unit Indoor unit Remote controller Central remote controller Option Over current breaker Fuse switch Earth leakage breaker Main switch Pull box PMV Kit Option 7 Installation of outdoor unit When using ...

Страница 18: ...erformed by power ON only 5 To set up an address the air conditioner does not need to be in operation 6 Manual address setup is also available besides automatic setup Automatic address Setup from SW15 on the interface P C board of the outdoor unit Manual address Setup from the wired remote controller It is temporarily necessary to set up the indoor unit as a 1 1 using a wired remote controller Aut...

Страница 19: ...12 13 14 Line address SW13 SW14 1 2 3 4 1 2 3 4 15 16 17 18 19 20 21 22 23 24 25 26 27 28 U2 U1 U3 U4 Relay connector For control wiring between indoor and outdoor For wiring of central control system 2 U 1 L08 U 1 flash Auto 1 Auto 2 Auto 3 U 1 U 1 flash U 1 U 1 light 8 When address setup has finished in all the systems turn off SW30 2 on the interface P C boards of the lines connected to the ide...

Страница 20: ...29 and 30 The address 29 and 30 cannot be set up in the outdoor unit Therefore if they are incorrectly set up a check code E04 Indoor outdoor communication circuit error will be displayed 2 When an address has been manually setup from the wired remote controller and you wish to set up a central control over the refrigeration system and setup the outdoor unit for each system using the following ste...

Страница 21: ...operates To select another system address 5 Push button to return to procedure 2 The indoor address of another line can be successively confirmed 6 Push button to finish the procedure 3 1 2 1 TEMP ON OFF SET TIME TEST FILTER RESET CL SAVE SWING FIX VENT UNIT LOUVER CODE No UNIT No R C No E D O M T E S R E M I T FAN SETDATA SETTING Operation procedure 1 2 3 End End VENT TEST TEST TEST 5 6 1 3 2 4 T...

Страница 22: ...ed from a wired remote controller 0099 is set up to line address indoor address and group address data from the wired remote controller For the setup procedure refer to the above mentioned address setup from the wired remote controller Method 2 Clear the indoor addresses in the same refrigerant system from the outdoor unit 1 Turn off the power of the refrigerant system to be returned to the status...

Страница 23: ...utdoor unit This air conditioner has a function which executes a test run by operation of the switches on the interface P C board of the outdoor unit This function is classified into Individual test run which performs a test run individually in each indoor unit and Collective test run which performs a test run for all the connected indoor units Individual test run Collective test run Procedure Ope...

Страница 24: ...quantity information IPDU communication error F04 TD1 sensor error F06 TE1 sensor error F07 TL sensor error F08 TO sensor error F12 01 TS1 sensor error TS1 sensor error F13 01 Compressor 1 TH sensor error F15 Outdoor temp sensor miswiring TE TL F16 Outdoor pressure sensor miswiring Pd Ps F23 Ps sensor error F24 Pd sensor error F31 Outdoor EEPROM error D600 A B D601 D602 D603 D604 H01 01 Compressor...

Страница 25: ... 24 MEMO ...

Страница 26: ... 25 MEMO ...

Страница 27: ... 26 MEMO ...

Страница 28: ... air conditioners is 0 3 kg m3 NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 15 kg NOTE 2 The standards...

Отзывы: