– 19 –
Manual address setup from remote controller
In case to decide an address of the indoor unit prior to finish of indoor electric wiring work and unpracticed outdoor
electric wiring work (Manual setup from wired remote controller)
Arrange indoor unit in which address is
set up and the wired remote controller to 1 : 1.
(Wiring example in 2 lines)
In the above example, under condition of
no inter-unit wire of the wired remote
controller, set the address after individual
connecting of the wired remote controller.
Group address
Operation procedure
1
→
2
→
3
→
4
→
5
→
6
→
7
→
8
→
9
→
10
→
11
End
Turn on the power.
1
Push simultaneously
+
+
buttons
for 4 seconds or more.
LCD changes to flashing.
2
Using the setup temp.
/
buttons,
set
to the CODE No.
3
Using the timer time
/
buttons, set up
the line address.
(Match it with the line address on the interface
P.C. board of the outdoor unit in the identical
refrigerant system.)
4
Push
button.
(OK when display goes on.)
5
Using the setup temp.
/
buttons,
set
to the CODE No.
6
Using the timer time
/
buttons, set up
the indoor address.
7
Push
button.
(OK when display goes on.)
8
Using the setup temp.
/
buttons,
set
to the CODE No.
9
Using the timer time
/
buttons, set
Individual =
, Header unit =
,
Follower unit =
.
10
Push
button.
(OK when display goes on.)
11
Push
button.
Setup operation finished.
(Status returns to normal stop status.)
Individual
: 0000
Header unit
: 0001
In case of group control
Follower unit
: 0002
1
1
1
1
2
2
1
3
2
2
1
2
2
2
2
Line address
Indoor address
Group address
Outdoor
Indoor
Remote
controller
Line 1
Line 2
Header
Follower
}}
SET
CL
TEST
(Line
address)
→
SET
(Indoor
address)
→
SET
(Group address)
→
SET
TEST
11
4, 7, 10
2, 5, 8
3, 6, 9
1
Data
CODE No.
NOTE
1. When setting the line address from the wired remote controller, do not use addresses
29
and
30
.
The address
29
and
30
cannot be set up in the outdoor unit. Therefore if they are incorrectly set up, a check
code
[E04]
(Indoor / outdoor communication circuit error) will be displayed.
2. When an address has been manually setup from the wired remote controller and you wish to set up a central
control over the refrigeration system and setup the outdoor unit for each system using the following steps.
• Using SW13 and 14 on the interface P.C. board of the header unit in each system, set up the line address for
each system.
• Turn off SW30-2 on all other interface P.C. boards on the header outdoor units that are connected to the same
central control, not including the system with the least number of address lines. (The terminator resistor of the
cables in the central control system of indoor / outdoor are unified.)
• Connect the relay connector between [U1U2] and [U3U4] of the header outdoor unit for each refrigerant
system.
• Then set up the central control address.
(For the central control address setup, refer to the Installation manual of the central control devices.)
Confirmation of indoor address and the main unit position on the
remote controller
Confirmation of indoor unit No. and position
1. When you want to know the indoor address though position of the indoor unit itself can be recognized;
•
In case of individual operation (Wired remote controller : Indoor unit = 1 : 1) or group control
[Procedure]
(Operation while the air conditioner operates)
1
If it stops, push
button.
2
Push
button.
The unit NO
is displayed on the LCD. (Disappears after several seconds)
The displayed unit number indicates the line address and indoor address. (If there is other indoor unit
connected to the same remote controller (Group control unit), other unit number is displayed every pushing
button.)
ON / OFF
2
1
CODE No.
ON / OFF
MODE
TEMP.
VENT
UNIT LOUVER
FAN
TIMER SET
TIME
SAVE
SWING/FIX
SET
CL
FILTER
RESET TEST
UNIT No.
Operation procedure
1
→
2
Operate
37-EN
38-EN