E6581467
3.4. Command & Setpoint selection (Local/Remote)
In case of switching setpoint and command between Local (terminal) and Remote (L
ON
W
ORKS
network), set the wiring like below figure and set the parameter as follows.
cmod
= 0
fmod
= 2
f112
= 48
Wiring
VF-S11
F
R
CC
P24
VIB
Setpoint
10k
Local/Remote switch
Command
4.7k-1/4W
Adjustment
10k
SINK
SW1
SOURCE
Note) If using VIB terminal for setpoint input, insert the proper resistor between P24 terminal and
setpoint potentiometer, because this option has no PP(10V) terminal.
Command
Setpoint
Control Terminal
Operation Panel
Serial Comm.(L
ON
W
ORKS
)
Internal potentiometer
VIA
VIB
Operation Panel
Serial Comm. (L
ON
W
ORKS
)
UP/DOWN
VIA + VIB
Serial Comm.
(L
ON
W
ORKS
)
cmod
fmod
Logic input = 48 (SC/LC)
Network cancel switch
Block diagrams
0
1
2
3
4
5
6
0
1
2
1
0
1
0
Serial Comm.
(L
ON
W
ORKS
)
*1: After the inverter power turned on and reset,
cmod
command and
fmod
setpoint are
activated until setting the command or setpoint from L
ON
W
ORKS
network. Set
cmod
and
fmod
to “Serial communication” to prevent this problem.
- 8 -