E6581467
4. Network variables
This L
ON
W
ORKS
option has the network variables to set and monitor the status, and the configuration
properties to set the configurations.
Header nci: Configuration
properties
nvi: Input network variables
nvo: Output network variables
N.B.: Never set the value out of valid range to network variables and configuration properties.
4.1. Object
map
This figure shows the LIU005Z object map.
Input Network Variables
Output Network Variables
LIU005Z
Network
Variables
nvoDrvSpeed
SNVT_lev_percent
nviDrvSpeedStpt
SNVT_switch
nviDrvSpeedScale
SNVT_lev_percent
nvoDrvPwr
SNVT_power_kilo
nvoDrvCurnt
SNVT_amp
nvoDrvVolt
SNVT_volt
nvoDrvRunHours
SNVT_time_hour
Configuration Properties
nciLocation
SNVT_str_asc
nciPwUpOutTm
SNVT_time_sec
nciRcvHrtBt
SNVT_time_sec
nciSndHrtBt
SNVT_time_sec
nciMinOutTm
SNVT_time_sec
nciMaxSpeed
SNVT_lev_percent
nciMinSpeed
SNVT_lev_percent
nciNmlSpeed
SNVT_rpm
nciNmlFreq
SNVT_freq_hz
nciRampUpTm
SNVT_time_sec
nciRampDownTm
SNVT_time_sec
nciDrvSpeedScale
SNVT_lev_percent
nvoInvP
nviInvP
nvoInvOutFreq
SNVT_freq_hz
nvoStatus
SNVT_obj_status
nviRequest
SNVT_obj_request
nvoDrvSpeedOtpt
SNVT_switch
nvoEmergStatus
SNVT_hvac_emerg
nvoDrvAlarm
SNVT_switch
nvoTypeVer
SNVT_str_asc
nviEmergOverride
SNVT_hvac_emerg
nviDrvReset
SNVT_state
nviInvSetFreq
SNVT_freq_hz
- 9 -