4.5.4. nviEmergOverride
(Emergency stop)
SNVT type: SNVT_have_emerg (103)
It provides an emergency stop of the motor. Emergency stop can be configured by Emergency stop
selection (
f603
) to coast stop, slow down stop or emergency DC braking (refer to the inverter
instruction manual for details).
- Valid range
Value Command
Description
0
Remove
emergency
EMERG_NORMAL (No Emergency mode)
1
EMERG_PRESSURIZE (Emergency pressurize mode)
2
EMERG_DEPRESSURIZE (Emergency depressurize
mode)
3
EMERG_PURGE (Emergency purge mode)
4
EMERG_SHUTDOWN (Emergency shutdown mode)
5
EMERG_FIRE (Emergency fire mode)
6 to 255
Emergency stop
---
N.B.: “Remove emergency” command clears a fault and resets the inverter.
4.5.5. nviDrvReset
(Reset command)
SNVT type: SNVT_state (83)
It provides a reset function for the inverter or the option unit. Reset is valid when the variable is sent after
setting specified bit.
- Valid range:
Field Operation
bit0
Reset the inverter (when the inverter is faulted)
bit1
Reset the option unit
bit2 to15
Invalid
N.B.: if both of bit0 and bit1 are set, it resets the option unit.