E6581467
4.4.10. nciRampUpTm
(Ramp Up Time)
SNVT type: SNVT_time_sec (107)
It determines the ramp up time of the motor.
- Valid range: 0.1 to 3200.0 sec.
- Unit: 0.1 sec.
- Default value: 10.0 sec.
N.B.: By editing this variable, this option unit changes the inverter parameter “
acc
” automatically.
4.4.11. nciRampDownTm
(Ramp Down Time)
SNVT type: SNVT_time_sec (107)
It determines the ramp down time of the motor.
- Valid range: 0.1 to 3200.0 sec.
- Unit: 0.1 sec.
- Default value: 10.0 sec.
N.B.: By editing this variable, this option unit changes the inverter parameter “
dec
” automatically.
4.4.12. nciDrvSpeedScale
(Default value for nviDrvSpeedScale)
SNVT type: SNVT_lev_percent (81)
It is used as the default value for “nviDrvSpeedScale”. When this option unit is initialized, it will be
updated.
- Valid range: -163.840 to 163.830%
- Unit: 0.005%
- Default value: 100.000%
- 15 -