4.4.7. nciMinSpeed
(
Minimum Speed
)
SNVT type: SNVT_lev_percent (81)
It is used to define the minimum speed of the inverter output. The value is entered as a percentage of
nominal frequency (nciNmlFreq). The value of the minimum speed must be validated against the value
of the maximum speed as follows:
- Valid range: 0.000 %
≤
minimum speed
≤
maximum speed
≤
100.000 %
(Limited within the value of the inverter parameter “
ll
” limitation)
- Unit: 0.005% (the resolution is depends on the inverter’s specification)
- Default Value: 0.000%
N.B.: After resetting the option, it updates the inverter parameter “
ll
”.
Danger
Do not set the value out of valid range.
Setting the value out of valid range may result in injuries by motor running
with unexpected speed.
Prohibited
4.4.8. nciNmlSpeed
(Nominal Motor Speed in min
-1
)
SNVT type: SNVT_rpm (102)
It is used to provide the nominal speed of the inverter output in min
-1
. This value is not used in the
option
- Valid range: 0 to 65534 min
-1
- Unit: 1 min
-1
- Default value: 1800 min
-1
4.4.9. nciNmlFreq
(Nominal Motor Frequency)
SNVT type: SNVT_freq_hz (76)
This configuration property is used to provide the nominal speed of the inverter output in Hz. This value
is used as the base speed on this option.
- Valid range: 30.0 to 500.0 Hz
- Unit: 0.1 Hz
- Default value: 60.0 Hz
N.B.: After resetting the option, it updates the inverter parameter “
fh
”.
Danger
Do not change this value while the motor is running.
Otherwise, It may result in injuries by motor running with unexpected speed.
Do not set the value out of valid range.
Otherwise, It may result in injuries by motor running with unexpected speed.
Prohibited