6F8A0917
- 78 -
Changing the hysteresis
The hysteresis value is set to 3% unless otherwise specified when the converter is shipped from the
factory.
The following is an example to show how to change the hysteresis value from 3% to 5%.
Switch operation
Display example
Description
C6: RANGE HYST
03.0 %
Select C6: RANGE HYST from the setting item selection
menu.
The currently set hysteresis value appears. (Note)
C6: RANGE HYST
03.0 %
The cursor appears.
C6: RANGE HYST
03.0 %
Move the cursor to the desired digit to change.
C6: RANGE HYST
05.0 %
Change the number of the digit.
To change other digit, press
under this condition to move
the cursor to that digit and change the number there.
C6: RANGE HYST
05.0 %
The display blinks and the set value is displayed for
confirmation.
Press
MENU/ENT
again to write the data. Then the cursor
disappears and the display returns to the condition that the
setting value is displayed.
C6: RANGE HYST
Returns to the menu of setting item selection.
Note: If you try to set a value exceeding 25.0%, *H. OVER SPEC.* appears and the value returns to
the previously set value. Try to set a new value again.