6F8A0917
- 117 -
Changing the fixed output constant
The following is an example to change the fixed pulse output value from 50pps to 100pps. To
change the fixed current output value, select the function “L2: FIX. CURR.”
Switch operation
Display example
Description
L3: FIX. PULSE
0050 pps
Select L3: FIX. PULSE from the setting item selection menu.
The currently set fixed pulse output value appears.
L3: FIX. PULSE
0050 pps
The cursor appears.
Press
further to move the cursor to the desired digit to
change.
L3: FIX. PULSE
0150 pps
↓
0100 pps
Change the number of the digit.
To change other digit, press
under this condition to move
the cursor to that digit and change the number there.
L3: FIX. PULSE
0100 pps
The display blinks and the set value is displayed for
confirmation.
Pres
MENU/ENT
again to write the data. Then the cursor
disappears and the display returns to the condition that the
setting value is displayed.
L3: FIX. PULSE
Returns to the menu of setting item selection.
Note: If you try to set a value outside of the settable range, the value will be forcibly set to the upper limit or the
lower limit of the settable range.