6F8C0879
23
3.2 Network Parameter Setting
3
(7) After downloading, switch off the base unit connected EN6 module.
(8) Change operation setting switch of EN6 module to [Setting from Tool (arbitrary
setting)]. (Setting from Tool: set address type IP0 and IP1 of operation mode
setting switch to on.
IP address free setting
If IPF ON and IP address type [Setting from Tool] are set using the operation mode
switches. IP addresses and subnet masks can be set free.
However, any of the following cannot be used for IP addresses.
• Address starting with 127 (7FH)
• Network address whose all bits are 0’s or 1’s
• Host address whose all bits are 0’s or 1’s
Subnet masks will have a value consisting of consecutive 1’s from the most significant
bit.
Note:
IP address free setting is valid for EN611, EN631, EN651, and EN651A only.
(It is not valid for EN621 and EN641 dual systems. If it is used, it is valid for line
A only, provided that a single socket interface is employed.)
3.2.2
Station address (Host ID) setting
Set a host ID with the host ID setting switches.
Any host ID may be set, provided that it is unique in the system. (Host ID = 1 to 126)
Host ID setting range is 01(h) to 7E(h).
If the IP address type is set to [Setting from Tool], however, the network ID has priority
over the value set with the host ID setting switches.