Direct Access Parameter Information
Deceleration Time 2
Program
Fundamental
ACC/DEC 1 – 4 Settings
This parameter specifies the time in seconds for the output of the
ASD to go from the Maximum Frequency to 0.0 Hz for the 2
Deceleration profile. The Accel/Decel pattern may be set using
.
This setting may be adjusted to stabilize unstable Virtual Linear
Pump operation.
This setting is also used to determine the deceleration rate of the
UP/DOWN Frequency Functions.
Note: A deceleration time shorter than the load will allow may
cause nuisance tripping and mechanical stress to loads.
Automatic Accel/Decel, Stall, and Ridethrough settings
may lengthen the deceleration times.
Direct Access Number —
F501
Parameter Type —
Numerical
Factory Default —
5.0
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 6000.0
Units — Seconds