Direct Access Parameter Information
https://www.toshiba.com/tic/
187
Over-Torque Detection Level During Regenerative Braking
Program
Protection
Over-Torque Parameters
This parameter sets the torque threshold level that is used as a
setpoint for over-torque tripping during negative torque (regen).
This setting is a percentage of the maximum rated torque of the
ASD.
.
Direct Access Number —
F617
Parameter Type —
Numerical
Factory Default —
250.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.00
Units — %
Over-Torque Detection Time
Program
Protection
Over-Torque Parameters
This parameter sets the amount of time that the over-torque con
-
dition may exceed the tripping threshold level set at
and
before a trip occurs.
.
Direct Access Number —
F618
Parameter Type —
Numerical
Factory Default —
0.50
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 10.00
Units — Seconds
Over-Torque Detection Hysteresis
Program
Protection
Over-Torque Parameters
During a momentary over-torque condition, this parameter pro
-
vides a torque threshold level to which the over-torque condition
must return within the time setting of
or an Over-Torque Trip
will be incurred.
Direct Access Number —
F619
Parameter Type —
Numerical
Factory Default —
10.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 100.00
Units — %
Cooling Fan Control
Program
Protection
Special Protection Parameters
This parameter sets the cooling fan run-time command.
Settings:
0 — Automatic
1 — Always On
Direct Access Number —
F620
Parameter Type —
Selection List
Factory Default —
Automatic
Changeable During Run —
Yes
Cumulative Operation Time Alarm Setting
Program
Protection
Special Protection Parameters
This parameter sets a run-time value that, once exceeded, closes
a discrete output contact. The output signal may be used to con
-
trol external equipment or used to engage a brake.
Associate the Total-Operation-Hours Alarm
to a discrete output contactor.
Note: The time displayed is 1/10th of the actual time (0.1 hr. = 1.0
hr.).
Direct Access Number —
F621
Parameter Type —
Numerical
Factory Default —
610.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 999.9
Units — Hours (X 10)
Содержание DN-68249-003
Страница 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Страница 2: ......
Страница 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Страница 305: ......