158
https://www.toshiba.com/tic/
Direct Access Parameter Information
Time-Based Alternation Emergency Timer
Program
Virtual Linear Pump
Time-Based Alternation
During Time-Based Alternation operation, in the event that the
Lead ASD trips or loses the transducer input signal, this parame
-
ter sets a counter time that will count down to zero.
Upon reaching zero, two actions will occur:
1) The Lag 1 ASD will accelerate to the setting of
at the
Accel Time 1
.
If the Lag1 ASD is tripped, another timer count begins and upon
reaching zero, the next available ASD will accelerate to the set
-
.
2) The system will check the load requirement of the Lag1 ASD
(or the next available ASD).
If the Lag 1 ASD load is zero, the ASD will stop.
If a non-zero load is detected, the Lag1 ASD will continue to run
in accordance with the user-set Virtual Linear Pump settings.
Time-Based Alternation
Time-Based Alternation (TBA) is used to provide a more evenly
distributed run-time of the system pumps of a multi-pump sys
-
tem. This is accomplished by varying which system pump plays
the Lead role.
Permanently assigning one pump as the Lead pump invariably
results in the Lead pump being over worked and requiring more
maintenance. The TBA algorithm allows the user to set the time
that each pump within the system is to be assigned the Lead
pump function and which are assigned the function of being the
Lag pump(s).
Upon completion of the user-set time, the system changes the
Lead pump assignment to the next pump number (
).
The Virtual Linear Pump feature allows the Lag pumps to assist
the Lead pump when required as the load exceeds the ability of
the lead pump.
Direct Access Number —
F404
Parameter Type —
Numerical
Factory Default —
60
Changeable During Run —
Yes
Minimum — 1
Maximum — 65535
Units — Minutes
Motor Rated Capacity (Nameplate)
Program
Motor
Vector Motor Model
This parameter is used to set the (nameplated) rated capacity of
the motor being used.
Direct Access Number —
F405
Parameter Type —
Numerical
Factory Default —
(ASD-Depen
-
dent)
Changeable During Run —
No
Minimum — (ASD-Dependent)
Maximum — (ASD-Dependent)
Units — kW
Содержание DN-68249-003
Страница 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Страница 2: ......
Страница 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Страница 305: ......