Direct Access Parameter Information
https://www.toshiba.com/tic/
219
Command Selection ()
Program
Communications
Modbus Settings
This parameter sets the command function to Prohibit or
Permit.
Settings:
0 — Prohibit
1 — Permit
Direct Access Number —
F816
Parameter Type —
Selection List
Factory Default —
Prohibit
Changeable During Run —
Yes
Number of Command ()
Program
Communications
Modbus Settings
This parameter is used to assign commands.
Settings:
0 — Prohibit
1 — Permit
Direct Access Number —
F817
Parameter Type —
Numerical
Factory Default —
0
Changeable During Run —
Yes
Minimum — 0
Maximum — 8
Number of Monitors ()
Program
Communications
Modbus Settings
This parameter is used to assign monitors.
Direct Access Number —
F818
Parameter Type —
Numerical
Factory Default —
0
Changeable During Run —
Yes
Minimum — 0
Maximum — 8
Command Station ()
Program
Communications
Modbus Settings
This parameter is used to assign the command station.
Direct Access Number —
F819
Parameter Type —
Numerical
Factory Default —
0
Changeable During Run —
Yes
Minimum — 0
Maximum — 64
Baud Rate (4-Wire RS485)
Program
Communications
Communication Settings
This parameter sets the RS485 baud rate.
Changes made to this parameter require that the power be
cycled (off then on) for the changes to take effect.
Settings:
0 — 9600 bps
1 — 19200 bps
2 — 38400 bps
Direct Access Number —
F820
Parameter Type —
Selection List
Factory Default —
19200
Changeable During Run —
Yes
Содержание DN-68249-003
Страница 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Страница 2: ......
Страница 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Страница 305: ......