Direct Access Parameter Information
Communication Time-Out (Modbus)
Program
Communications
Ethernet Settings
This parameter plays a role in the setup of the communications
network by setting the time that no activity may exist over the
communications link before the link is severed (Time Out).
The communications network includes other ASDs and Host/
Control computers that monitor the status of the ASD(s), trans
-
fers commands, and loads or modifies the parameter settings of
the ASD.
Changes made to this parameter require that the power be
cycled (Off then On) for the changes to take effect.
Direct Access Number —
F594
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 60.0
Motor Overload Protection Level 1
Program
Fundamental
Motor Set 1
This parameter specifies the motor overload current level for
Motor Set 1. This value is entered as either a percentage of the
full load rating of the ASD or as a percentage of the FLA of the
motor.
The unit of measurement for this parameter may be set to A/V
(Amps) or it may be set as a percentage of the ASD rating. The
nameplated FLA of the motor may be entered directly when
Amps is selected as the unit of measurement (use
to
change the display unit).
Motor Overload Protection Level 1 settings will be displayed in
Amps if the EOI display units are set to A/V rather than %.
Direct Access Number —
F600
Parameter Type —
Numerical
Factory Default —
100
Changeable During Run —
Yes
Minimum — 10
Maximum — 100
Units — %
Stall Prevention Level
Program
Protection
Stall
This parameter specifies the output current level at which the out
-
put frequency is reduced in an attempt to prevent a trip. The over-
current level is entered as a percentage of the maximum rating of
the ASD.
Note: The Motor Overload Protection parameter must be enabled
Direct Access Number —
F601
Parameter Type —
Numerical
Factory Default —
150
Changeable During Run —
Yes
Minimum — 10
Maximum — 165
Units — %
Содержание DN-68249-003
Страница 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Страница 2: ......
Страница 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Страница 305: ......