Direct Access Parameter Information
https://www.toshiba.com/tic/
77
Forward/Reverse Run
Program
Fundamental
Standard Mode Selection
While operating in the
Local
mode, this parameter sets the direc
-
tion of motor rotation.
From the Frequency Command screen, press the ESC key. At the
subsequent EOI Command screen, select the Direction field and
change the setting. Press the Rotary Encoder and the new set
-
ting will be in effect.
This setting
(Forward/Reverse
Disable).
If either direction is disabled via parameter
, the disabled
direction will not be recognized if commanded by the keypad. If
both directions are disabled via parameter
, the direction
command from the keypad will determine the direction of the
motor rotation.
Settings:
0 — Forward
1 — Reverse
2 — Forward (Switchable F/R by Keypad)
3 — Reverse (Switchable F/R by Keypad)
Direct Access Number —
F008
Parameter Type —
Selection List
Factory Default —
Forward
Changeable During Run —
Yes
Acceleration Time 1
Program
Fundamental
Accel/Decel 1 Settings
This parameter specifies the time in seconds for the output of the
ASD to go from 0.0 Hz to the Maximum Frequency for the Accel
-
eration 1 profile. The Accel/Decel pattern may be set using
Note: An acceleration time shorter than that which the load will
allow may cause nuisance tripping and mechanical stress
to loads. Automatic Accel/Decel, Stall, and Ridethrough
settings may lengthen the acceleration times.
Acceleration
The acceleration rate of a motor is determined by several fac
-
tors: applied power, applied load, and the physical properties of
the motor (winding parameters, motor size, etc.). The ASD will
control the first of these factors: input power. The settings of the
ASD will control the frequency and amplitude of the applied volt
-
age to the motor.
Under most operating conditions, as the output frequency of the
ASD goes up so does the output voltage (linear acceleration).
The ASD has the ability to modify the relationship between fre
-
quency and voltage automatically to produce smoother operation
or increased (starting) torque (see
).
Direct Access Number —
F009
Parameter Type —
Numerical
Factory Default —
(ASD-Depen
-
dent)
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 6000.0
Units — Seconds
Содержание DN-68249-003
Страница 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Страница 2: ......
Страница 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Страница 305: ......