Direct Access Parameter Information
https://www.toshiba.com/tic/
175
Acceleration/Deceleration Pattern 1
Program
Special
ACC/DEC 1 – 4 Settings
This parameter enables a user-selected preprogrammed output
profile that controls the acceleration and deceleration pattern for
the 1 Accel/Decel
).
Settings:
0 — Linear
1 — S-Pattern 1
2 — S-Pattern 2
The figures below provide a profile of the available accel/decel
patterns.
Direct Access Number —
F502
Parameter Type —
Selection List
Factory Default —
Linear
Changeable During Run —
Yes
Linear
acceleration and deceleration is
the default pattern and is used on most
applications.
S-pattern 1
is used for applications that
require quick acceleration and
deceleration. This setting is also popular
for applications that require shock
absorption at the start of acceleration or
deceleration.
S-pattern 2
decreases the rate of
change above the base frequency for
acceleration and deceleration.