High-Wall Type
Installation Manual
– 40 –
Toshiba
EN
L10
(L29)
SIM
Outdoor unit P.C.
board
Outdoor
In the case of outdoor P.C. board
jumper wire (for service) setting
error
Entire
stop
L20
SIM
LAN communication
error
Network
adapter
central
control
Address setting, central control
remote controller, network
adapter --- Duplication of
address in central control
communication
Auto-
reset
L29
SIM
Other outdoor unit
error
Outdoor
Other outdoor unit error
Entire
stop
1) Communication error between
IPDU MCU and CDB MCU
Entire
stop
2) Abnormal temperature was
detected by the heat sink temp.
sensor in IGBT.
L30
SIM
Abnormal external
input into indoor unit
(interlock)
Indoor
External devices, outdoor unit
P.C. board --- Abnormal stop due
to incorrect external input into
CN80
Entire
stop
L31
SIM
Phase sequence
error, etc.
Outdoor
Power supply phase sequence,
outdoor unit P.C. board ---
Abnormal phase sequence of the
3-phase power supply
Operatio
n
continue
d
(thermos
tat OFF)
P01
ALT
Indoor unit fan error
Indoor
Indoor fan motor, indoor P.C.
board --- Indoor AC fan error (fan
motor thermal relay activated)
was detected.
Entire
stop
P03
ALT
Outdoor unit
discharge temp. error
Outdoor
An error was detected in the
discharge temp. releasing
control.
Entire
stop
P04
ALT
Outdoor unit high-
pressure system
error
Outdoor
High-pressure switch --- The IOL
was activated or an error was
detected in the high-pressure
releasing control using the TE.
Entire
stop
P05
ALT
Open phase detected Outdoor
The power cable may be
connected incorrectly. Check
open phase and voltage of the
power supply.
Entire
stop
P07
ALT
Heat sink overheat
Outdoor
Abnormal temperature was
detected by the temp. sensor of
the IGBT heat sink.
Entire
stop
P10
ALT
Indoor unit water
overflow detected
Indoor
Drain pipe, clogging of drainage,
float switch circuit, indoor P.C.
board --- Drainage is out of order
or the float switch was activated.
Entire
stop
P15
ALT
Gas leakage
detected
Outdoor
There may be gas leakage from
the pipe or connecting part.
Check for gas leakage.
Entire
stop
P19
ALT
4-way valve error
Outdoor
(Indoor)
4-way valve, indoor temp.
sensors (TC/TCJ) --- An error
was detected due to temperature
drop of the indoor unit heat
exchanger sensor when heating.
Auto-
reset
(Auto-
reset)
P20
ALT
High-pressure
protective operation
Outdoor
High-pressure protection
Entire
stop
P22
ALT
Outdoor unit fan error Outdoor
Outdoor unit fan motor, outdoor
unit P.C. board --- An error (over
current, locking, etc.) was
detected in the outdoor unit fan
drive circuit.
Entire
stop
40-EN