High-Wall Type
Installation Manual
– 27 –
Toshiba
Procedure
5
1. Using temp. setup
/
buttons,
specify CODE No. [
14
].
(CODE No. [
14
]: Group address)
2. Using timer time
/
buttons, change
the SET DATA from [
0001
] to [
0002
].
(SET DATA [Header unit:
0001
] [Follower
unit:
0002
])
3. Push
button.
In this time, the setup finishes when the
display changes from flashing to lighting.
Procedure
6
If there is other indoor unit to be changed, repeat
procedure
2
to
5
to change the setup.
When the above setup has finished, push
to select the indoor UNIT No. before change of
setup, specify CODE No. [
12
], [
13
], [
14
] in order
with temp. setup
/
buttons, and then
check the changed contents.
Address change check Before change:
[
3-3-1
]
→
After change: [
2-2-2
]
Pushing
button clears the contents of which
setup was changed.
(In this case, procedure from
2
is repeated.)
Procedure
7
After check of the changed contents, push
button. (Setup is determined.) When pushing
button, the display disappears and the status
becomes the usual stop status. (When pushing
button the operation from the remote controller is
not accepted for approx. 1 minute.)
* If the operation from the remote controller is not
accepted even 1 minute or more passed after
pushing
button, it is considered that the
address setup is incorrect.
In this case, the automatic address must be
again set up.
Therefore repeat procedure of the setup change
from the Procedure
1
.
To recognize the position of the
corresponding indoor unit though the
indoor UNIT No. is known
Check the position during operation stop.
(Be sure to stop operation of the set.)
Indoor UNIT No. before setup change is displayed.
Indoor UNIT No. before setup change is displayed.
2
1,3
1
27-EN