– 3 –

3

Selection of installation place

WARNING

Install the air conditioner securely in a location where the base can sustain the weight adequately.

If the strength is not enough, the unit may fall down resulting in injury.

Install the air conditioner at a height 8’ (2.4 m) or more from the floor.

If you insert your hands or others directly into the unit while the air conditioner operates, it is dangerous because you 
may contact with revolving fan or active electricity.

CAUTION

Do not install in a location where flammable gas may leaks are possible.

If the gas leak and accumulate around the unit, it may ignite and cause a fire.

Upon approval of the customer, install the air conditioner in a place that satisfies the following 

conditions.

• Place where the unit can be installed horizontally.
• Place where a sufficient servicing space can be ensured for safety maintenance and check.
• Place where drained water will not cause any problem.

Avoid installing in the following places.

• Place exposed to air with high salt content (seaside area), or place exposed to large quantities of sulfide gas (hot 

spring). 
(The unit should be used in these places, special protective measures are needed.)

• A restaurant kitchen where a lot of oil is used or place near machines in a factory (Oil adhering to the heat 

exchanger and resin part (turbo fan) in the indoor unit may reduce the performance, generate mist or dew drop, 
or deform or damage resin parts.)

• Places where iron or other metal dust is present. If iron or other metal dust adheres to or collects on the interior 

of the air conditioner, it may spontaneously combust and start a fire.

• Place where organic solvent is used nearby.
• Place close to a machine generating high frequency.
• Place where the discharged air blows directly into the window of the neighbor house. (Outdoor unit)
• Place where noise of the outdoor unit is easily transmitted.

(When the outdoor unit is installed on the boundary with the neighbor, pay due attention to the level of noise.)

• Place with poor ventilation. (Before air duct work, check whether value of fan speed, static pressure and duct 

resistance are correct.)

• Do not use the air conditioner for special purposes such as preserving food, precision instruments, or art objects, 

or where breeding animals or growing plants are kept. (This may degrade the quality of preserved materials.)

• Place where any of high-frequency appliances (including inverter devices, private power generators, medical 

equipment, and communication equipment) and inverter-type fluorescent light is installed. 
(A malfunction of the air conditioner, abnormal control, or problems due to noise to such appliances/equipment 
may occur.)

• When the wireless remote control is used in a room equipped with an inverter-type fluorescent light or at a place 

exposed to direct sunlight, signals from the remote control may not be received correctly.

• Place where organic solvent is used.
• Place near a door or window exposed to humid outside air (Dew drop may form.).
• Place where special spray is used frequently.

Installation space

Ensure there is sufficient space to install the unit and to perform maintenance work as and when required. Keep 
0.6” (15 mm) or more for clearance between top plate of the indoor unit and the ceiling surface.

unit: in (mm)

Selection of installation place

Continual operation of the indoor unit under high-humidity conditions as described below, dew may condense and 
water may drop.
Especially, high-humidity atmosphere (dew point temperature: 73.4 °F (23 °C) or more) may generate dew inside 
the ceiling.
1. Unit is installed inside the ceiling with slated roof.
2. Unit is installed at a location using inside of the ceiling as fresh air take-in path.
3. Kitchen

Advice

• Set a service check opening panel at right side of the unit (size: 17.7" × 17.7" (450 × 450 mm) or more) for piping, 

maintenance, and servicing.

• If installing a unit at such place, put insulating material (glass wool, etc.) additionally on all the positions of the 

indoor unit which come to contact with high-humidity atmosphere.

REQUIREMENT

When the humidity inside the ceiling seems to be higher than 80 %, attach a heat insulator to the side (top) 
surface of the indoor unit. (Use a heat insulator that is 0.4" (10 mm) or more thick.)

Obstacle

39.4” (1000) or more

39.4” (1000

or

 m

ore

11.1” (2

83) or m

ore

0.6” (1

5) or mo

re

7.9” (20

0)

Check port

17.7” (450)

5-EN

6-EN

+00EH99876101-2_00Ta.book  Page 3  Monday, September 1, 2014  10:15 AM

Содержание Carrier MMU-AP0071MH2UL

Страница 1: ...lti 18 Français Indoor Unit Model name Compact 4 way Cassette type MMU AP0071MH2UL MMU AP0091MH2UL MMU AP0121MH2UL MMU AP0151MH2UL MMU AP0181MH2UL AIR CONDITIONER MULTI TYPE Installation Manual For commercial use Pour usage commercial 00EH99876101 2_00Ta book Page 1 Monday September 1 2014 10 15 AM ...

Страница 2: ...sold parts The Ceiling panel and remote control are sold separately For the installation of these products follow the Installation Manuals supplied with them Part name Q ty Shape Usage Installation Manual 1 This manual Hand over to customers Heat insulating pipe 2 For heat insulation of pipe connecting section Installation pattern 1 For confirmation of ceiling opening and indoor unit position Inst...

Страница 3: ...ixed in the refrigerant the gas pressure in the refrigeration cycle becomes abnormally high and it resultingly causes pipe burst and injuries on persons Perform installation work properly according to the Installation Manual Inappropriate installation may result in water leakage electric shock or fire When the air conditioner is installed in a small room provide appropriate measures to ensure that...

Страница 4: ...t resistance are correct Do not use the air conditioner for special purposes such as preserving food precision instruments or art objects or where breeding animals or growing plants are kept This may degrade the quality of preserved materials Place where any of high frequency appliances including inverter devices private power generators medical equipment and communication equipment and inverter t...

Страница 5: ... the air conditioning unit must be positioned in a location that can sufficiently support its weight and give protection against adverse environmental conditions Failure to do so may result in unit damage and possible human injury Any incomplete installation may also cause possible risk of human injury Unpack the package take out the product and then place it on the floor so that the same surface ...

Страница 6: ...oning a ceiling opening and hanging bolts For new ceiling Use the installation pattern to position the ceiling opening when a ceiling is hanged After the hanging bolts have been installed install the indoor unit To use the supplied pattern attach it to the indoor unit using the supplied fixing screws 0 2 5 mm 0 6 16 mm 4 pcs Screw pattern to the ceiling panel hanging brackets of the indoor unit Be...

Страница 7: ...er Accessory To prevent the bolt from falling off for safety be sure to set it just under the hanging bracket as shown in the figure Eccentric washer Accessory Nut 3 8 M10 Hanging bolt 3 8 M10 Nut 3 8 M10 Procure hanging bolts and nuts locally Install with the marking UP facing up Indoor unit Level vial levelness 0 2 5 mm or less Hanging bolt Hanging bracket Installation gauge 1 0 4 1 7 10 42 mm C...

Страница 8: ...esive agent cannot be used for the pipe connecting port hard socket of the indoor unit Be sure to use the attached hose band for fixing otherwise damage or water leakage of the drain pipe connecting port is caused Connecting drain pipe Connect a hard socket locally procured to the hard socket of the attached supplied flexible hose Connect a drain pipe locally procured to the connected hard socket ...

Страница 9: ...0 8 mm or more thickness 2 Flare nut and flare works are also different from those of the conventional refrigerant Take out the flare nut attached to the main unit of the air conditioner and use it REQUIREMENT When the refrigerant pipe is long provide support brackets at intervals of 8 2 9 10 2 5 3 m to clamp the refrigerant pipe Otherwise abnormal sound may be generated CAUTION IMPORTANT 4 POINTS...

Страница 10: ...ward ceiling side Banding band locally procured 7 Electrical connection WARNING 1 Use predefined wire and connect them certainly Keep the connecting terminal free from external force Improper wire connection or clamping may result in exothermic fire or malfunction 2 Connect ground wire grounding work Incomplete grounding cause an electric shock Do not connect ground wires to gas pipes water pipes ...

Страница 11: ...Wire size AWG20 Total wire length of remote control wiring and remote control inter unit wiring L L1 L2 Ln In case of wired type only Up to 1640 5 500 m In case of wireless type included Up to 1312 4 400 m Total wire length of remote control inter unit wiring L1 L2 Ln Up to 656 2 200 m L1 L L2 Ln Indoor unit Remote control inter unit wiring Indoor unit Indoor unit Indoor unit Remote control Max 8 ...

Страница 12: ...1 U2 A B L1 L2 L1 L2 Screw Cover of electrical control box Electrical control box Screw Wire cover Conduit plate B Screw Conduit plate A Screw Lock nut Conduit plate A Conduit pipe Adhered surface Slit section Heat insulator A Ground screw for shielded wire Power supply terminal block Control wire 2 core shielded wire Control wire connecting port Control wire Remote control terminal block Cord cla...

Страница 13: ...elected unit runs and the louvers start swinging The indoor unit can be confirmed for which to change settings 1 6 1 3 2 5 4 Display content varies with the indoor unit model 3 Specify CODE No with temp setup buttons 4 Select SET DATA with timer time buttons 5 Push button When the display changes from flashing to lit the setup is completed To change settings of another indoor unit repeat from Proc...

Страница 14: ...setup refer to the Installation Manual attached to the outdoor unit SET DATA Filter sign lighting time 0000 None 0001 150 H 0002 2500 H Factory default 0003 5000 H 0004 10000 H SET DATA Detection temp shift value 0000 No shift 0001 1 8 F 1 C 0002 3 6 F 2 C Factory default 0003 5 4 F 3 C 0004 7 2 F 4 C 0005 9 0 F 5 C 0006 10 8 F 6 C SET DATA 0000 0001 Remote control sensor Not used factory default ...

Страница 15: ...No appear on the display part of the remote control The check code is only displayed during the operation If the display disappears operate the air conditioner according to the following Confirmation of error log for confirmation Confirmation of error log When an error occurred on the air conditioner the error log can be confirmed with the following procedure The error log is stored in memory up t...

Страница 16: ...16 E16 00 Capacity over 01 No of connected units Capacity over No of connected indoor units I F E18 Communication error between indoor units Indoor E19 E19 00 Header is nothing 02 Two or more header units Outdoor header units quantity error I F E20 E20 01 Outdoor of other line connected 02 Indoor of other line connected Other line connected during automatic address I F E23 E23 Sending error in com...

Страница 17: ...d remote control display Outdoor 7 segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash A3 IPDU Fan IPDU 1 2 3 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F IPDU error Error detected by TCC LINK central control device TCC LINK TOSHIBA Carrier Communication Link P18 P18 ALT Discharge temp TD3 error I F P19 P19 Detected outdoor unit number ALT 4 way valve ...

Страница 18: ...ystems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 22 lbs 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 33 lbs 15 kg NOTE 2 The standards for minimum room volume are as follows 1 No partition shaded ...

Страница 19: ...ILING 3 0003 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively For check method refer to Applicable controls in this manual Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10...

Отзывы: