Toshiba Carrier MMU-AP0071MH2UL Скачать руководство пользователя страница 16

– 15 –

Check codes and parts to be checked

Check method

On the remote control (Wired remote control, Central control remote control) and the interface P.C. board of the 
outdoor unit (I/F), a check display LCD (Remote control) or 7-segment display (on the outdoor interface P.C. board) 
to display the operation is provided. Therefore the operation status can be known. With this self-diagnosis function, 
a trouble or position with error of the air conditioner can be found as shown in the table below.

Check code list

The following list shows each check code. Find the check contents from the list according to part to be checked.
• To check from indoor remote control: See “Wired remote control display” in the list.
• To check from outdoor unit: See “Outdoor 7-segment display” in the list.
• To check from indoor unit with a wireless remote control: See “Sensor block display of receiving unit” in the list.

IPDU : Intelligent Power Drive Unit

: Lighting, 

: Flashing, 

: Goes off

ALT. : Flashing is alternately when there are two flashing LED.
SIM : Simultaneous flashing when there are two flashing LED.

Check code

Wireless remote control

Check code name

Judging device

Wired remote 

control display

Outdoor 7-segment display

Sensor block display of 

receiving unit

Auxiliary code

Operation Timer Ready Flash

E01

Communication error between indoor and remote 

control 

(Detected at remote control side)

Remote control

E02

Remote control transmission error

Remote control

E03

Communication error between indoor and remote 

control (Detected at indoor side)

Indoor

E04

Communication circuit error between indoor/

outdoor (Detected at indoor side)

Indoor

E06

E06

No. of indoor units in which 

sensor has been normally 

received

Decrease of No. of indoor units

I/F

E07

Communication circuit error between indoor/

outdoor (Detected at outdoor side)

I/F

E08

E08 Duplicated indoor addresses

Duplicated indoor addresses

Indoor / I/F

E09

Duplicated header remote controls

Remote control

E10

Communication error between indoor MCU

Indoor

E12

E12

01: Indoor/Outdoor 

communication

02: Communication between 

outdoor units

Automatic address start error

I/F

E15

E15

Indoor is nothing during automatic addressing

I/F

E16

E16 00: Capacity over

01 ~:No. of connected units

Capacity over / No. of connected indoor units

I/F

E18

Communication error between indoor units

Indoor

E19

E19 00: Header is nothing

02: Two or more header units

Outdoor header units quantity error

I/F

E20

E20

01: Outdoor of other line 

connected

02: Indoor of other line connected

Other line connected during automatic

address

I/F

E23

E23

Sending error in communication between

outdoor units

I/F

E25

E25

Duplicated follower outdoor addresses

I/F

E26

E26 No. of outdoor units which 

received signal normally

Decrease of No. of connected outdoor units

I/F

E28

E28 Detected outdoor unit number

Follower outdoor unit error

I/F

E31

E31

IPDU communication error

I/F

F01

ALT Indoor TCJ sensor error

Indoor

F02

ALT Indoor TC2 sensor error

Indoor

F03

ALT Indoor TC1 sensor error

Indoor

F04

F04

ALT TD1 sensor error

I/F

F05

F05

ALT TD2 sensor error

I/F

F06

F06 TE1 sensor

TE2 sensor

ALT TE1 sensor error

TE2 sensor error

I/F

F07

F07

ALT TL sensor error

I/F

F08

F08

ALT TO sensor error

I/F

F10

ALT Indoor TA sensor error

Indoor

F12

F12

ALT TS1 sensor error

I/F

F13

F13

01: Comp. 1 side

02: Comp. 2 side

03: Comp. 3 side 

ALT TH sensor error

IPDU

F15

F15

ALT Outdoor temp. sensor miswiring (TE1, TL)

I/F

F16

F16

ALT Outdoor pressure sensor miswiring (Pd, Ps)

I/F

F22

F22

ALT TD3 error

I/F

F23

F23

ALT Ps sensor error

I/F

F24

F24

ALT Pd sensor error

I/F

F29

SIM Indoor other error

Indoor

F31

F31

SIM Indoor EEPROM error

I/F

H01

H01

01: Comp. 1 side

02: Comp. 2 side

03: Comp. 3 side

Compressor break down

IPDU

H02

H02

01: Comp. 1 side

02: Comp. 2 side

03: Comp. 3 side

Compressor trouble (lock)

IPDU

H03

H03

01: Comp. 1 side

02: Comp. 2 side

03: Comp. 3 side

Current detect circuit system error

IPDU

H05

H05

TD1 miswiring

I/F

H06

H06

Low pressure protective operation

I/F

H07

H07

Oil level down detective protection

I/F

H08

H08

01: TK1 sensor error

02: TK2 sensor error

03: TK3 sensor error

04: TK4 sensor error

Oil level detective temp sensor error

I/F

H15

H15

TD2 miswiring

I/F

Check code

Wireless remote control

Check code name

Judging device

Wired remote 

control display

Outdoor 7-segment display

Sensor block display of 

receiving unit

Auxiliary code

Operation Timer Ready Flash

A3-IPDU

Fan 

IPDU

1

2

3

01

02

03

04

05

06

07

08

09

0A

0B

0C

0D

0E

0F

 : IPDU error

29-EN

30-EN

+00EH99876101-2_00Ta.book  Page 15  Monday, September 1, 2014  10:15 AM

Содержание Carrier MMU-AP0071MH2UL

Страница 1: ...lti 18 Français Indoor Unit Model name Compact 4 way Cassette type MMU AP0071MH2UL MMU AP0091MH2UL MMU AP0121MH2UL MMU AP0151MH2UL MMU AP0181MH2UL AIR CONDITIONER MULTI TYPE Installation Manual For commercial use Pour usage commercial 00EH99876101 2_00Ta book Page 1 Monday September 1 2014 10 15 AM ...

Страница 2: ...sold parts The Ceiling panel and remote control are sold separately For the installation of these products follow the Installation Manuals supplied with them Part name Q ty Shape Usage Installation Manual 1 This manual Hand over to customers Heat insulating pipe 2 For heat insulation of pipe connecting section Installation pattern 1 For confirmation of ceiling opening and indoor unit position Inst...

Страница 3: ...ixed in the refrigerant the gas pressure in the refrigeration cycle becomes abnormally high and it resultingly causes pipe burst and injuries on persons Perform installation work properly according to the Installation Manual Inappropriate installation may result in water leakage electric shock or fire When the air conditioner is installed in a small room provide appropriate measures to ensure that...

Страница 4: ...t resistance are correct Do not use the air conditioner for special purposes such as preserving food precision instruments or art objects or where breeding animals or growing plants are kept This may degrade the quality of preserved materials Place where any of high frequency appliances including inverter devices private power generators medical equipment and communication equipment and inverter t...

Страница 5: ... the air conditioning unit must be positioned in a location that can sufficiently support its weight and give protection against adverse environmental conditions Failure to do so may result in unit damage and possible human injury Any incomplete installation may also cause possible risk of human injury Unpack the package take out the product and then place it on the floor so that the same surface ...

Страница 6: ...oning a ceiling opening and hanging bolts For new ceiling Use the installation pattern to position the ceiling opening when a ceiling is hanged After the hanging bolts have been installed install the indoor unit To use the supplied pattern attach it to the indoor unit using the supplied fixing screws 0 2 5 mm 0 6 16 mm 4 pcs Screw pattern to the ceiling panel hanging brackets of the indoor unit Be...

Страница 7: ...er Accessory To prevent the bolt from falling off for safety be sure to set it just under the hanging bracket as shown in the figure Eccentric washer Accessory Nut 3 8 M10 Hanging bolt 3 8 M10 Nut 3 8 M10 Procure hanging bolts and nuts locally Install with the marking UP facing up Indoor unit Level vial levelness 0 2 5 mm or less Hanging bolt Hanging bracket Installation gauge 1 0 4 1 7 10 42 mm C...

Страница 8: ...esive agent cannot be used for the pipe connecting port hard socket of the indoor unit Be sure to use the attached hose band for fixing otherwise damage or water leakage of the drain pipe connecting port is caused Connecting drain pipe Connect a hard socket locally procured to the hard socket of the attached supplied flexible hose Connect a drain pipe locally procured to the connected hard socket ...

Страница 9: ...0 8 mm or more thickness 2 Flare nut and flare works are also different from those of the conventional refrigerant Take out the flare nut attached to the main unit of the air conditioner and use it REQUIREMENT When the refrigerant pipe is long provide support brackets at intervals of 8 2 9 10 2 5 3 m to clamp the refrigerant pipe Otherwise abnormal sound may be generated CAUTION IMPORTANT 4 POINTS...

Страница 10: ...ward ceiling side Banding band locally procured 7 Electrical connection WARNING 1 Use predefined wire and connect them certainly Keep the connecting terminal free from external force Improper wire connection or clamping may result in exothermic fire or malfunction 2 Connect ground wire grounding work Incomplete grounding cause an electric shock Do not connect ground wires to gas pipes water pipes ...

Страница 11: ...Wire size AWG20 Total wire length of remote control wiring and remote control inter unit wiring L L1 L2 Ln In case of wired type only Up to 1640 5 500 m In case of wireless type included Up to 1312 4 400 m Total wire length of remote control inter unit wiring L1 L2 Ln Up to 656 2 200 m L1 L L2 Ln Indoor unit Remote control inter unit wiring Indoor unit Indoor unit Indoor unit Remote control Max 8 ...

Страница 12: ...1 U2 A B L1 L2 L1 L2 Screw Cover of electrical control box Electrical control box Screw Wire cover Conduit plate B Screw Conduit plate A Screw Lock nut Conduit plate A Conduit pipe Adhered surface Slit section Heat insulator A Ground screw for shielded wire Power supply terminal block Control wire 2 core shielded wire Control wire connecting port Control wire Remote control terminal block Cord cla...

Страница 13: ...elected unit runs and the louvers start swinging The indoor unit can be confirmed for which to change settings 1 6 1 3 2 5 4 Display content varies with the indoor unit model 3 Specify CODE No with temp setup buttons 4 Select SET DATA with timer time buttons 5 Push button When the display changes from flashing to lit the setup is completed To change settings of another indoor unit repeat from Proc...

Страница 14: ...setup refer to the Installation Manual attached to the outdoor unit SET DATA Filter sign lighting time 0000 None 0001 150 H 0002 2500 H Factory default 0003 5000 H 0004 10000 H SET DATA Detection temp shift value 0000 No shift 0001 1 8 F 1 C 0002 3 6 F 2 C Factory default 0003 5 4 F 3 C 0004 7 2 F 4 C 0005 9 0 F 5 C 0006 10 8 F 6 C SET DATA 0000 0001 Remote control sensor Not used factory default ...

Страница 15: ...No appear on the display part of the remote control The check code is only displayed during the operation If the display disappears operate the air conditioner according to the following Confirmation of error log for confirmation Confirmation of error log When an error occurred on the air conditioner the error log can be confirmed with the following procedure The error log is stored in memory up t...

Страница 16: ...16 E16 00 Capacity over 01 No of connected units Capacity over No of connected indoor units I F E18 Communication error between indoor units Indoor E19 E19 00 Header is nothing 02 Two or more header units Outdoor header units quantity error I F E20 E20 01 Outdoor of other line connected 02 Indoor of other line connected Other line connected during automatic address I F E23 E23 Sending error in com...

Страница 17: ...d remote control display Outdoor 7 segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash A3 IPDU Fan IPDU 1 2 3 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F IPDU error Error detected by TCC LINK central control device TCC LINK TOSHIBA Carrier Communication Link P18 P18 ALT Discharge temp TD3 error I F P19 P19 Detected outdoor unit number ALT 4 way valve ...

Страница 18: ...ystems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 22 lbs 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 33 lbs 15 kg NOTE 2 The standards for minimum room volume are as follows 1 No partition shaded ...

Страница 19: ...ILING 3 0003 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively For check method refer to Applicable controls in this manual Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10...

Отзывы: