background image

– 9 –

Tightening connection

CAUTION

• Do not apply excessive torque. Otherwise, the nut 

may crack depending on the conditions.

Tightening torque of flare pipe connections

Pressure of R410A is higher than that of R22.
(Approx. 1.6 times) Use a torque wrench, tighten the 
flare pipe connecting sections which connect the 
indoor and outdoor units of the specified tightening 
torque.
Incorrect connections may cause not only a gas leak, 
but also a trouble of the refrigeration cycle.
Align the centers of the connecting pipes and tighten 
the flare nut as far as possible with your fingers. Then 
tighten the nut with a spanner and torque wrench as 
shown in the figure.

REQUIREMENT

Tightening with an excessive torque may crack the nut 
depending on installation conditions.
Tighten the nut within the specified tightening torque.

Piping with outdoor unit

• Shape of valve differs according to the outdoor unit.

For details of installation, refer to the Installation 
Manual of the outdoor unit.

Leak check test, evacuation 
and other procedure

For leak check test, evacuation, addition of refrigerant, 
and gas leak check, refer to the Installation Manual 
attached to the outdoor unit.

REQUIREMENT

Do not supply power to the indoor unit until the leak 
check test and evacuation are completed. (If the indoor 
unit is powered on, the pulse motor valve is fully closed, 
which extends the time for vacuuming.)

Open the valve fully

Open the valve of the outdoor unit fully.
For details, refer to the Installation Manual attached to 
the outdoor unit.

Heat insulation process

Apply heat insulation for the pipes separately at liquid 
side and gas side.
For the heat insulation to the pipes at gas side, use the 
material with heat-resisting temperature 248 °F (120 
°C) or higher.
Apply the attached heat insulation to the pipe 
connecting section of the indoor unit securely without 
gap.

REQUIREMENT

• Apply the heat insulation to the pipe connecting 

section of the indoor unit securely up to the root 
without exposure of the pipe. (The pipe exposed to the 
outside may causes water leak.)

• Wrap heat insulator with its slits facing up (ceiling 

side).

Unit: ft•lbs (N•m)

Outer dia. of copper pipe

Tightening torque

1/4” (6.4 mm)

10 - 13 (14 - 18)

3/8” (9.5 mm)

24 - 31 (33 - 42)

1/2” (12.7 mm)

37 - 46 (50 - 62)

Work using double spanner

Indoor unit

Union

Heat insulation 

pipe 

(Accessory)

Flare nut

Heat insulator 

of the pipe

Wrap the pipe with the attached heat insulator 

without any gap between the indoor unit.

The seam must be faced upward 

(ceiling side).

Banding band 

(locally 

procured)

7

Electrical connection

WARNING

1.

Use predefined wire and connect them certainly. 
Keep the connecting terminal free from external 
force.

Improper wire connection or clamping may result in 
exothermic, fire or malfunction.

2.

Connect ground wire. (grounding work)

Incomplete grounding cause an electric shock.
Do not connect ground wires to gas pipes, water 
pipes, lightning rods or ground wires for telephone 
wires.

3.

Install appliance in accordance with national 
wiring regulations.

Capacity shortage of circuit breaker or incomplete 
installation may cause an electric shock or a fire.

CAUTION

• Consult local building codes, NEC (National Electrical 

Code) or CEC (Canadian Electrical Code) for special 
requirements.

• If incorrect / incomplete wiring is carried out, it will 

cause an electrical fire or smoke.

• Install circuit breaker is not tripped by shock waves.

If circuit breaker is not installed, an electric shock may 
be caused.

• Use the cord clamps attached to the product.
• Do not damage or scratch the conductive core and 

inner insulator of power and control wires when 
peeling them.

• Use the power cord and control wire of specified 

thickness, type, and protective devices required.

• Do not connect 208/230 V power to the terminal 

blocks (U1, U2, A, B etc.) for control wiring.
(Otherwise, the system will fail.)

• Perform the electric wiring so that it does not come to 

contact with the high-temperature part of the pipe.
The coating may melt resulting in an accident.

• Do not turn on the circuit breaker of the indoor unit 

until vacuuming of the refrigerant pipes completes.

REQUIREMENT

• For power supply wiring, strictly conform to the Local 

Regulation in each country.

• Run the refrigerant piping line and control wiring line in 

the same line.

Power supply wire and 
control wires specifications

Power supply wire and control wires are procured 
locally.
For the power supply specifications, follow to the table 
below. If capacity is little, it is dangerous because 
overheat or seizure may be caused.

Indoor unit power supply

• For the power supply of the indoor unit, prepare the 

exclusive power supply separated from that of the 
outdoor unit.

Power supply

Control wiring, Central control wiring

• 2-core with non-polarity wires are used for the 

control wiring between indoor unit and outdoor unit 
and Central control wiring.

• To prevent noise trouble, use 2-core shielded wire.
• The length of the communication line means the total 

length of the control wire length between indoor and 
outdoor units added with the central control wire 
length.

Power supply

208/230-1-60

17-EN

18-EN

+00EH99876101-2_00Ta.book  Page 9  Monday, September 1, 2014  10:15 AM

Содержание Carrier MMU-AP0071MH2UL

Страница 1: ...lti 18 Français Indoor Unit Model name Compact 4 way Cassette type MMU AP0071MH2UL MMU AP0091MH2UL MMU AP0121MH2UL MMU AP0151MH2UL MMU AP0181MH2UL AIR CONDITIONER MULTI TYPE Installation Manual For commercial use Pour usage commercial 00EH99876101 2_00Ta book Page 1 Monday September 1 2014 10 15 AM ...

Страница 2: ...sold parts The Ceiling panel and remote control are sold separately For the installation of these products follow the Installation Manuals supplied with them Part name Q ty Shape Usage Installation Manual 1 This manual Hand over to customers Heat insulating pipe 2 For heat insulation of pipe connecting section Installation pattern 1 For confirmation of ceiling opening and indoor unit position Inst...

Страница 3: ...ixed in the refrigerant the gas pressure in the refrigeration cycle becomes abnormally high and it resultingly causes pipe burst and injuries on persons Perform installation work properly according to the Installation Manual Inappropriate installation may result in water leakage electric shock or fire When the air conditioner is installed in a small room provide appropriate measures to ensure that...

Страница 4: ...t resistance are correct Do not use the air conditioner for special purposes such as preserving food precision instruments or art objects or where breeding animals or growing plants are kept This may degrade the quality of preserved materials Place where any of high frequency appliances including inverter devices private power generators medical equipment and communication equipment and inverter t...

Страница 5: ... the air conditioning unit must be positioned in a location that can sufficiently support its weight and give protection against adverse environmental conditions Failure to do so may result in unit damage and possible human injury Any incomplete installation may also cause possible risk of human injury Unpack the package take out the product and then place it on the floor so that the same surface ...

Страница 6: ...oning a ceiling opening and hanging bolts For new ceiling Use the installation pattern to position the ceiling opening when a ceiling is hanged After the hanging bolts have been installed install the indoor unit To use the supplied pattern attach it to the indoor unit using the supplied fixing screws 0 2 5 mm 0 6 16 mm 4 pcs Screw pattern to the ceiling panel hanging brackets of the indoor unit Be...

Страница 7: ...er Accessory To prevent the bolt from falling off for safety be sure to set it just under the hanging bracket as shown in the figure Eccentric washer Accessory Nut 3 8 M10 Hanging bolt 3 8 M10 Nut 3 8 M10 Procure hanging bolts and nuts locally Install with the marking UP facing up Indoor unit Level vial levelness 0 2 5 mm or less Hanging bolt Hanging bracket Installation gauge 1 0 4 1 7 10 42 mm C...

Страница 8: ...esive agent cannot be used for the pipe connecting port hard socket of the indoor unit Be sure to use the attached hose band for fixing otherwise damage or water leakage of the drain pipe connecting port is caused Connecting drain pipe Connect a hard socket locally procured to the hard socket of the attached supplied flexible hose Connect a drain pipe locally procured to the connected hard socket ...

Страница 9: ...0 8 mm or more thickness 2 Flare nut and flare works are also different from those of the conventional refrigerant Take out the flare nut attached to the main unit of the air conditioner and use it REQUIREMENT When the refrigerant pipe is long provide support brackets at intervals of 8 2 9 10 2 5 3 m to clamp the refrigerant pipe Otherwise abnormal sound may be generated CAUTION IMPORTANT 4 POINTS...

Страница 10: ...ward ceiling side Banding band locally procured 7 Electrical connection WARNING 1 Use predefined wire and connect them certainly Keep the connecting terminal free from external force Improper wire connection or clamping may result in exothermic fire or malfunction 2 Connect ground wire grounding work Incomplete grounding cause an electric shock Do not connect ground wires to gas pipes water pipes ...

Страница 11: ...Wire size AWG20 Total wire length of remote control wiring and remote control inter unit wiring L L1 L2 Ln In case of wired type only Up to 1640 5 500 m In case of wireless type included Up to 1312 4 400 m Total wire length of remote control inter unit wiring L1 L2 Ln Up to 656 2 200 m L1 L L2 Ln Indoor unit Remote control inter unit wiring Indoor unit Indoor unit Indoor unit Remote control Max 8 ...

Страница 12: ...1 U2 A B L1 L2 L1 L2 Screw Cover of electrical control box Electrical control box Screw Wire cover Conduit plate B Screw Conduit plate A Screw Lock nut Conduit plate A Conduit pipe Adhered surface Slit section Heat insulator A Ground screw for shielded wire Power supply terminal block Control wire 2 core shielded wire Control wire connecting port Control wire Remote control terminal block Cord cla...

Страница 13: ...elected unit runs and the louvers start swinging The indoor unit can be confirmed for which to change settings 1 6 1 3 2 5 4 Display content varies with the indoor unit model 3 Specify CODE No with temp setup buttons 4 Select SET DATA with timer time buttons 5 Push button When the display changes from flashing to lit the setup is completed To change settings of another indoor unit repeat from Proc...

Страница 14: ...setup refer to the Installation Manual attached to the outdoor unit SET DATA Filter sign lighting time 0000 None 0001 150 H 0002 2500 H Factory default 0003 5000 H 0004 10000 H SET DATA Detection temp shift value 0000 No shift 0001 1 8 F 1 C 0002 3 6 F 2 C Factory default 0003 5 4 F 3 C 0004 7 2 F 4 C 0005 9 0 F 5 C 0006 10 8 F 6 C SET DATA 0000 0001 Remote control sensor Not used factory default ...

Страница 15: ...No appear on the display part of the remote control The check code is only displayed during the operation If the display disappears operate the air conditioner according to the following Confirmation of error log for confirmation Confirmation of error log When an error occurred on the air conditioner the error log can be confirmed with the following procedure The error log is stored in memory up t...

Страница 16: ...16 E16 00 Capacity over 01 No of connected units Capacity over No of connected indoor units I F E18 Communication error between indoor units Indoor E19 E19 00 Header is nothing 02 Two or more header units Outdoor header units quantity error I F E20 E20 01 Outdoor of other line connected 02 Indoor of other line connected Other line connected during automatic address I F E23 E23 Sending error in com...

Страница 17: ...d remote control display Outdoor 7 segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash A3 IPDU Fan IPDU 1 2 3 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F IPDU error Error detected by TCC LINK central control device TCC LINK TOSHIBA Carrier Communication Link P18 P18 ALT Discharge temp TD3 error I F P19 P19 Detected outdoor unit number ALT 4 way valve ...

Страница 18: ...ystems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 22 lbs 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 33 lbs 15 kg NOTE 2 The standards for minimum room volume are as follows 1 No partition shaded ...

Страница 19: ...ILING 3 0003 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively For check method refer to Applicable controls in this manual Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10...

Отзывы: