5
Outdoor unit
52
Combination unit (System with Non-ducted indoor units)
(*1) Rated conditions
Cooling: Indoor air temperature 80 °F DryBulb/67 °F WetBulb, Outdoor air temperature 95 °F DryBulb
Heating: Indoor air temperature 70 °F DryBulb, Outdoor air temperature 47 °F DryBulb/43 °F WetBulb
Equivalent piping length: 100 ft, Height difference: 0 ft
(*2) Value for only outdoor unit
(*3) Setting is necessary
(*4) The amount does not consider extra piping length. Refrigerant must be added on site in accordance with the actual piping length.
(*5) High-pressure switch / High-pressure sensor / Low-pressure sensor / Fusible plug / PC board fuse / Inverter overload protector
(*6) Select wire size based on the larger value of MCA.
MCA: Minimum Circuit Amps (minimum circuit Amps required for power supply design.)
(*7) MOCP: Maximum Overcurrent Protection (Amps)
(*8) This specification is value as of June, 2013, please note that specification is subject to change without notice.
Outdoor unit set model name
MMY-
AP1444HT6UL
AP1684HT6UL
AP1924HT6UL
AP2284HT6UL
Outdoor unit model name
MMY-
MAP0724HT6UL
MAP0724HT6UL
MAP0964HT6UL
MAP0724HT6UL
MAP0964HT6UL
MAP0964HT6UL
MAP1144HT6UL
MAP1144HT6UL
Power Supply
Nominal voltage
V/Ph/Hz
460 / 3 / 60
Voltage range
V
414 Minimum / 506 Maximum
Cooling
Nominal capacity
(*1)
kBtu/h
144
168
192
228
Rated capacity
138
160
184
228
Rated power consumption
(*2)
kW
12.38
14.66
16.94
21.11
Rated EER
Btu/W
11.1
10.9
10.9
10.8
Heating
Nominal capacity
(*1)
kBtu/h
162
189
216
2
48
Rated capacity
162
188
212
248
Rated power consumption
(*2)
kW
13.75
16.95
19.12
21.32
Rated COP
W/W
3.45
3.25
3.25
3.41
Starting Current
A
Soft Start
Total Weight
Packed
lbs
654 + 654
855 + 654
855 + 855
855 + 855
Unit
lbs
621 + 621
817 + 621
817 + 817
817 + 817
Color
Silky shade (Munsell 1Y8.5/0.5)
Compressor
Type
Hermetic twin rotary compressor
Motor output
kW
2.3 × 2 + 2.3 × 2
2.1 × 3 + 2.3 × 2
2.1 × 3 + 2.1 × 3
2.5 × 3 + 2.5 × 3
Fan unit
Fan
Propeller fan
Motor output
kW
1.0 + 1.0
1.0 + 1.0
1.0 + 1.0
1.0 + 1.0
Air volume
cfm
5,800 + 5,800
6,600 + 5,800
6,600 + 6,600
7,060 + 7,060
Maximum external static pressure
(*3) In WG
0.20
0.20
0.20
0.20
Heat exchanger
Finned tube
Refrigerant
Name
R410A
Charged refrigerant amount
(*4)
lbs
25.4 + 25.4
25.4 + 25.4
152025.4 + 25.4
25.4 + 25.4
High-pressure switch
psi
OFF: 420 ON: 540
Protective devices
(*5)
Electrical
specifications
Unit
MCA
(*6)
A
18 + 18
23 + 18
23 + 23
24 + 24
MOCP
(*7)
A
20 + 20
25 + 20
25 + 25
25 + 25
Refrigerant
piping
Liquid
Type
Flare connection
Diameter
In
5/8"
5/8"
5/8"
3/4"
Suction
gas
Type
Brazing connection
Diameter
In
1-1/8"
1-1/8"
1-1/8"
1-3/8"
Balance
Type
Flare connection
Diameter
In
3/8"
3/8"
3/8"
3/8"
Indoor units
Maximum capacity of combined indoor units
80 to 125%
Maximum number of indoor units
24
28
32
38
Operation temperature range
Cooling FDB
23
to
115
Heating
FWB
-4 to 60
Sound pressure level
Cooling
dB(A)
59.0
61.5
63.0
65.0
Heating
dB(A)
60.0
63.5
65.0
66.0
Содержание Carrier MMC-AP0181H2UL
Страница 60: ...5 Outdoor unit 59 5 2 2 Heat pump 5 2 2 1 Single unit Model MMY MAP0724HT9UL MAP0724HT6UL 72 9 ...
Страница 61: ...5 Outdoor unit 60 Model MMY MAP0964HT9UL MAP0964HT6UL MMY MAP1144HT9UL MAP1144HT6UL 72 9 ...
Страница 75: ...5 Outdoor unit 74 5 6 Wiring diagram 5 6 1 Heat recovery Model MMY MAP0724FT9UL 208 230 V 60 Hz ...
Страница 76: ...5 Outdoor unit 75 Model MMY MAP0724FT6UL 460 V 60 Hz WHI WHI WHI PUR ...
Страница 77: ...5 Outdoor unit 76 Model MMY MAP0964FT9UL MAP1204FT9UL 208 230 V 60 Hz ...
Страница 78: ...5 Outdoor unit 77 Model MMY MAP0964FT6UL MAP1204FT6UL 460 V 60 Hz WHI WHI WHI PUR ...
Страница 79: ...5 Outdoor unit 78 5 6 2 Heat pump Model MMY MAP0724HT9UL ...
Страница 80: ...5 Outdoor unit 79 Model MMY MAP0724HT6UL ...
Страница 81: ...5 Outdoor unit 80 Model MMY MAP0964HT9UL MAP1144HT9UL ...
Страница 82: ...5 Outdoor unit 81 Model MMY MAP0964HT6UL MAP1144HT6UL ...
Страница 212: ...MEMO ...
Страница 213: ...Engineering Data Book For North America August 2015 First Edition ...