Safety caution
2
Safety caution
Warnings on refrigerant leakage
Check of Concentration Limit
The room in which the air conditioner is to be
installed requires a design that in the event of
refrigerant gas leaking out, its concentration will not
exceed a set limit.
The refrigerant R410A which is used in the air
conditioner is safe, without the toxicity or combustibility
of ammonia, and is not restricted by laws to be imposed
which protect the ozone layer. However, since it
contains more than air, it poses the risk of suffocation if
its concentration should rise excessively. Suffocation
from leakage of R410A is almost non-existent. With the
recent increase in the number of high concentration
buildings, however, the installation of multi air
conditioner systems is on the increase because of the
need for effective use of floor space, individual control,
energy conservation by curtailing heat and carrying
power etc. Most importantly, the multi air conditioner
system is able to replenish a large amount of refrigerant
compared with conventional individual air conditioners.
If a single unit of the multi conditioner system is to be
installed in a small room, select a suitable model and
installation procedure so that if the refrigerant
accidentally leaks out, its concentration does not reach
the limit (and in the event of an emergency, measures
can be made before injury can occur). In a room where
the concentration may exceed the limit, create an
opening with adjacent rooms, or install mechanical
ventilation combined with a gas leak detection device.
The concentration is as given below.
Concentration limit
Compliance to the local applicable regulations and
standards for the concentration limit is required.
NOTE 1 :
If there are 2 or more refrigerating systems in a single
refrigerating device, the amounts of refrigerant should
be as charged in each independent device.
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in
rooms A, B and C is 22 lbs (10 kg).
The possible amount of leaked refrigerant gas in
rooms D, E and F is 33 lbs (15 kg).
NOTE 2 :
The standards for minimum room volume are as follows.
(1) No partition (shaded portion)
(2) When there is an effective opening with the adjacent
room for ventilation of leaking refrigerant gas
(opening without a door, or an opening 0.15% or
larger than the respective floor spaces at the top or
bottom of the door).
(3) If an indoor unit is installed in each partitioned room
and the refrigerant piping is interconnected, the
smallest room of course becomes the object. But
when a mechanical ventilation is installed interlocked
with a gas leakage detector in the smallest room
where the density limit is exceeded, the volume of
the next smallest room becomes the object.
Total amount of refrigerant (lbs (kg))
Min. volume of the indoor unit installed room (ft
3
(m
3
))
≤
Concentration limit (lbs/ft
3
(kg/m
3
))
Outdoor unit
e.g., charged amount
((22 lbs) 10 kg)
e.g.,charged amount
(33 lbs (15 kg))
Room A
Indoor unit
Room B Room C Room D Room E Room F
Important
Outdoor unit
Refrigerant piping
Indoor unit
Outdoor unit
Mechanical ventilation device - Gas leak detector
Indoor unit
Very
small
room
Small
room
Medium
room
Large
room
Refrigerant piping
Содержание Carrier MMC-AP0181H2UL
Страница 60: ...5 Outdoor unit 59 5 2 2 Heat pump 5 2 2 1 Single unit Model MMY MAP0724HT9UL MAP0724HT6UL 72 9 ...
Страница 61: ...5 Outdoor unit 60 Model MMY MAP0964HT9UL MAP0964HT6UL MMY MAP1144HT9UL MAP1144HT6UL 72 9 ...
Страница 75: ...5 Outdoor unit 74 5 6 Wiring diagram 5 6 1 Heat recovery Model MMY MAP0724FT9UL 208 230 V 60 Hz ...
Страница 76: ...5 Outdoor unit 75 Model MMY MAP0724FT6UL 460 V 60 Hz WHI WHI WHI PUR ...
Страница 77: ...5 Outdoor unit 76 Model MMY MAP0964FT9UL MAP1204FT9UL 208 230 V 60 Hz ...
Страница 78: ...5 Outdoor unit 77 Model MMY MAP0964FT6UL MAP1204FT6UL 460 V 60 Hz WHI WHI WHI PUR ...
Страница 79: ...5 Outdoor unit 78 5 6 2 Heat pump Model MMY MAP0724HT9UL ...
Страница 80: ...5 Outdoor unit 79 Model MMY MAP0724HT6UL ...
Страница 81: ...5 Outdoor unit 80 Model MMY MAP0964HT9UL MAP1144HT9UL ...
Страница 82: ...5 Outdoor unit 81 Model MMY MAP0964HT6UL MAP1144HT6UL ...
Страница 212: ...MEMO ...
Страница 213: ...Engineering Data Book For North America August 2015 First Edition ...