5
Outdoor unit
92
Model
name
Appearance
Function
TCB-
PCIN4UL
Size: 2.87 × 3.11 (in)
[3] Operating Rate Output
Application
* Install the optional
PCB in the inverter
assembly of the
outdoor header unit.
Function
The state of operation is available to check remotely as the signal of
system operation rate enable to output.
Operation
As shown in the table, each of the output terminals turns ON (relay
closes) and OFF (relay opens) depending on the system operating rate.
OFF=relay open ON=relay closed
Wiring example
Functions
SW16
OUTPUT1 OUTPUT2 OUTPUT3 Operating rate FA
System
operating
rate output bit 1: ON
bit 2: OFF
OFF
OFF
OFF
FA = 0%
ON
OFF
OFF
0% < FA < 20%
OFF
ON
OFF
20%
≤
FA < 35%
ON
ON
OFF
35%
≤
FA < 50%
OFF
OFF
ON
50%
≤
FA < 65%
ON
OFF
ON
65%
≤
FA < 80%
OFF
ON
ON
80%
≤
FA < 95%
ON
ON
ON
95%
≤
FA
C2
Attached connection cable 2 (5wires)
CN514
Connector on interface side (green)
K1, K2, K3
Relays
MONITOR
Monitoring device
OUTPUT1
Output terminal for each function
OUTPUT2
Output terminal for each function
OUTPUT3
Output terminal for each function
PJ20
Connector on optional PCB side
TB1
Terminal block
1
ON
OFF
2 3 4
OUTPUT1
PJ20
OUTPUT2
OUTPUT3
TB1
1
2
5
6
4
3
C2
K1
K2
K3
1
ON
OFF
2 3 4
SW16
MONITOR
Outdoor unit
interface PCB
Optional PCB
Locally procured
Header outdoor unit
Shield
wire
CN514
Содержание Carrier MMC-AP0181H2UL
Страница 60: ...5 Outdoor unit 59 5 2 2 Heat pump 5 2 2 1 Single unit Model MMY MAP0724HT9UL MAP0724HT6UL 72 9 ...
Страница 61: ...5 Outdoor unit 60 Model MMY MAP0964HT9UL MAP0964HT6UL MMY MAP1144HT9UL MAP1144HT6UL 72 9 ...
Страница 75: ...5 Outdoor unit 74 5 6 Wiring diagram 5 6 1 Heat recovery Model MMY MAP0724FT9UL 208 230 V 60 Hz ...
Страница 76: ...5 Outdoor unit 75 Model MMY MAP0724FT6UL 460 V 60 Hz WHI WHI WHI PUR ...
Страница 77: ...5 Outdoor unit 76 Model MMY MAP0964FT9UL MAP1204FT9UL 208 230 V 60 Hz ...
Страница 78: ...5 Outdoor unit 77 Model MMY MAP0964FT6UL MAP1204FT6UL 460 V 60 Hz WHI WHI WHI PUR ...
Страница 79: ...5 Outdoor unit 78 5 6 2 Heat pump Model MMY MAP0724HT9UL ...
Страница 80: ...5 Outdoor unit 79 Model MMY MAP0724HT6UL ...
Страница 81: ...5 Outdoor unit 80 Model MMY MAP0964HT9UL MAP1144HT9UL ...
Страница 82: ...5 Outdoor unit 81 Model MMY MAP0964HT6UL MAP1144HT6UL ...
Страница 212: ...MEMO ...
Страница 213: ...Engineering Data Book For North America August 2015 First Edition ...