31
that must be used with care and only if the factory was contacted first. See the “Reset to Factory Settings” help for
more details.
Voltage: Nominal voltage of the controller
FLC: Full load current rating of the motor.
LRC: Lock rotor current rating of the motor. Unless specified, this value is automatically set to six times the FLC.
Phase: Input power number of phases.
Frequency: Input power frequency.
Transition Timer: Will set the time for which a motor is in the temporary starting wiring configuration. When this
timer expires, the motor will be wired in delta.
Starter: Motor starter configuration. This value is read-only.
Serial: Serial number of the controller. This value is read-only.
Model: Model number of the controller. This value is read-only.
Program: Program version of the ViZiTouch. This value is read-only.
Reset to Factory Settings Page
This page will reset the ViZiTouch to the original factory configuration, thus clearing all subsequent configurations
performed during the life of the controller.
This procedure should only be used as a last attempt to bring back the controller to a usable state.
User “Level 2”:
The “RESET” button will be activated (will become blue) only if no square buttons from the left column are activated
and the “Last Saved Settings” from the right column is not activated as well. A “Level 2” user can only reset the
“Factory Settings” and/or the “Additional Settings” from the right column.
The “Factory Settings” reset will restore the controller to its original factory configuration and service state. This
means that the first service will be undone, automatic mode settings, as well as the
controller’s “Homepage” will be
deactivated until “First Service” is completed again. Please refer to the “Quick Start-Up” guide for more information
on how to perform the “First Start-Up” and how to complete the “Field Acceptance Test Report”.