- IO Electric Communication Error: Activates if no communication with the electric IO card could be established for
15 seconds. This alarm is critical and triggers the bell. If this alarm persists for more than 1 minute, the controller
will reboot to try to fix the problem.
- IO Expansion Communication Error: Activates if no communication with the Expansion IO card could be
established for 15 seconds.
- Communication System Failure: Activates when the communication task has stopped responding. This alarm
condition is critical and the controller will reboot to try to fix the problem.
- File System Failure: Activates when a file system error was detected. This alarm condition is critical and the
controller will reboot to try to fix the problem.
- Pump on demand: Activates when the pressure is below the cut-in set-point on an automatic pressure actuated
controller.