TECHNICAL DESCRIPTION
The main section bar/crossbar of the automation is made of high resistance anodized extruded aluminum. The
gearmotors, toothed belts and electronic control circuits are incorporated in a covered casing in anodized extruded
aluminum, fastened by fitting for more rapid, simple access in case of maintenance. The carriages supporting the door
are made of sheet steel, and are equipped with high-density plastic wheels with lifetime lubrication of the bearings, on a
rail inside the main section bar/crossbar. The transmission and movement via two gearmotors function on a wormscrew
with lifetime lubrication and a toothed belt in anti-static rubber material with steel cable strands that are long-lasting and
wear-resistant. Electronic control circuits are a microprocessor type with keys for adjustment of the parameters such as
speed of opening and closure, slowing space, low approach speed, automatic reclosing time and mode of operation. The
movement, position and speed of the door are managed by electronic control circuits via a reading device and optical
encoder installed on gearmotor.
The automation is electromechanical, without clutch or brakes, to prevent possible blockage of a continuous nature due to
damages or breakage of the structure.
The power supply is 230V~ 50/60 Hz with low voltage transformer 22V AC ~ 150VA.
Safety anti-crushing device on both closure and opening, that enables the door to reverse its movement if it meets an
obstacle.
5.2
EMERGENCY BATTERY
3) Set “parameter 5: Emergency battery”, without a dot (no dot after the 5 on the display);
6) Connect the wire to the emergency battery again;
In the event that the battery is fully discharged, the time required to fully recharge it is
10 hours.
Door operation in emergency case:
The automation equipped with an emergency battery, will perform, in case of
power failure, the “default battery operation mode”: the “continuous operation mode” and will continue to operate as
set as in the selector program. The "battery operation mode" can be changed in other modes, using the Topp DS2
digital program switch. Emergency opening or closing can be set. In the case has been selected a different mode
operation than the standard one, the automation will resume to function as the program set by the selector after
restoring the 230V mains.
2) Enter the programming function, see Chap.5.6 Programming parameters;
5) Disconnect the emergency battery wire;
To recharge the battery, proceed as follows:
7) Plug into the 230V mains;
8) Charge the battery for 24 hours.
Supervision and automatic testing of the emergency battery:
The emergency battery function is kept under constant
control by the electronic microprocessor control circuit. This supervision and test constantly verifies the efficiency of the
battery that, in case of malfunction, blocks the door and thereby signals the malfunction. Emergency opening or closure
depends on the function entered in the program setting of the electronic circuit board.
Contact a qualified technician in the event that the battery requires replacement;
Emergency battery performance:
To ensure the maximum performance of the emergency batteries and prevent their
deterioration, the batteries should be recharged every 3 months in case of disuse or for products in storage.
When the key is installed, the emergency battery will not act in case of power outage, until the key is pressed.
Manual emergency opening:
When it is required that the emergency opening not be performed automatically in case of
power outage on the 230V mains, it is possible to install a key for management of this function.
1) Switch on automation / electronic unit;
4) Exit the programming function. Disconnect power to the automation/electronic unit from the 230V mains (see Chap.4.4
Electrical connections);
5.3
BRING THE CARD AS FACTORY: ORIGINAL SETTINGS
Ÿ
At this point, the card will wait to be reset (
see para. 5.4
).
The first start-up function serves to return the card to the original factory settings.
This procedure will delete all the previous settings, except:
Ÿ
Error history; Counters; Cycles and expiry dates of the maintenance menù.
Ÿ
After 4 seconds, the card is placed in the "FIRST START" and the 7-segment display the letter "A" flashing.
Ÿ
Remove 230V power and disconnect the battery from the circuit board;
Ÿ
Simultaneously press the two buttons "ENTER" and "DOWN" on the electronic board (see Figure 26);
Ÿ
Connect the battery 24V and return power to the circuit board 230 by continuing to hold the two keys "ENTER" and
"DOWN";
Instructions for performing this procedure: