Toky AI208 Series Скачать руководство пользователя страница 9

9/10 page                                                                          KKAI208C01A-A1-20140904

1                             2                               3                               4                               5                                6                         7 

0xC8                     0xB9                     0xD2

Meter ADD                 Function ID            Data byte 

                                                                   number  

Data1

high

Client normal answer(Read multi-register

Data1

low

CRC code

low bit

CRC code

low bit

0x01                       0x03                           0x02                                                 

0x00

Function ID abnormal answer:

For example:host request ADD is 0x2011

1                    2                          3                        4                   5

0x01                 0x83                  0x02                  0xC0              0xF1

Meter ADD       Function ID

Error code

Client abnormal answer(Read multi-register)

CRC code low CRC code high

1                2              3                4               5               6               7                8               9              10             11

0x01         0x10          0x20         0x00        0x00          0x01          0x02          0x00         0x96

2

Write multi-register

Host request

write multi-register

For example:Host write float integer SV

setting value 150

       ADD code of SV is 0x2000,because SV is integer(2 dyte),seizes 1 data register.The memory code of decimal integer 150 is 0x0096.

Data location error response:(For example:Host request the ADD index is 0x200F)

1                    2                   3                              4                      5   

0x01                 0x90                   0x03                 0x0C              0x01

Meter ADD       Function ID

Error code

Abnormal response(Write multi-register)

CRC low

CRC high

Data 

high

Meter ADD

Start ADD

High bit

Start ADD

Low bit

Data byte

Length/

high bit

Data byte

Length/

high bit

Data byte

length

Function ID

Data 

low

CRC code

low bit

CRC code

high bit

0x07

0xFC

Address Mapping Table of Meter Parameters

0x2000

0x2001

0x2002

0x2003

0x2004

0x2005

0x2006

0x2007

0x2008

0x2009

0x200A

1

2

3

4

5

6

7

8

9

10

11

Set value SV
1st loop alarm AL1

1st loop alarm backlash HY1

2nd loop alarm AL2

2nd loop alarm backlash HY2

Display low limit FL

Display high limit FH

Analog output low limit BRL

Analog output high limit BRH

Control output low limit OLL

No decimal point

No decimal point

No decimal point

Default with 

1 decimal point

Control output high limit OLH

No.

ADD mapping

Variable name

Register

Read/write

Remark

1

1

1

1

1

1

1

1

1

1

1

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

0x200B

0x200C

0x200D

0x200E

0x200F

0x2010

12

13

14

15

16

17

Heat & Cool control dead zone DB

Overshoot limit OVS

Proportional coefficient of cooling PC

Translation correct PS

Dispaly fuzzy tracking value DTR

Measure value PV

1

1

1

1

1

R/W

1

R/W

R/W

R/W

R

R

Содержание AI208 Series

Страница 1: ...ault 10 Please tighten screw torque according to the rules If not it may lead to electric shock and fire 11 In order not to interfere with this products to dissipate heat please don t plug casing arou...

Страница 2: ...ted pair with a shield for remote RS485 communication cable and deal with the shield on the host side earth otherwise it will reduce the effect of noise filter 8 This product is not the fuse please se...

Страница 3: ...solation Note when there is no analog output communication port between and part of specification such as relay output is isolation SSR output is no isolation Name of universal panel R S Menu key ensu...

Страница 4: ...de and after power on long press SET key more than 3s to enter the menu parameters to ckeck the type b In the checking mode in menu you can press SET each short time to check the manu parameters recur...

Страница 5: ...nalog range low limit Analog range high limit note the value is reverse analog output when it less than analog range low limit Output low limit limit the output low limit current amplitude Setting val...

Страница 6: ...ose the function Temperature unit F Line signal input unit engineering work Digits User auto calibrating enable function this parameter is only for use of input signal expect TC RTD Y user of enable a...

Страница 7: ...normal room temperature please back to monitoring mode or input the load power and long press AT enter auto tuning mode now AT indicator will shine 7 Auto tuning will take the time in order not to af...

Страница 8: ...2 dyte seizes 2 data register The memory code of decimal integer 200 is 0x00C8 Note It should read DP value or ensure DP value in first to ensure the decimal point when reading data and need to transf...

Страница 9: ...ponse Write multi register CRC low CRC high Data high MeterADD StartADD Highbit StartADD Lowbit Databyte Length highbit Data byte Length high bit Databyte length FunctionID Data low CRCcode lowbit CRC...

Страница 10: ...DD ADD Communication baud rate BAD Communication relay setting DTC Optional input signal INP 1st loop alarm type AD1 2nd loop alarm type AD2 D7 D6 D5 D4 D3 D2 D1 D0 AT AL2 AL1 OUT2 OUT1 R Read R W Rea...

Отзывы: