Toky AI208 Series Скачать руководство пользователя страница 7

4:(48*48)

6:(96*48)

7:(72*72)

8:(48*96)

9:(96*96)

80:(80*160)

16:(160*80)

48

48

72

96

96

160

80

Model

A

H(Min)

   

G

B

C

D

E

F

J

48

96

72

48

96

80

160

97.5

97.5

97.5

97.5

97.5

96

96

6.5

9

9

9

9

13

13

91

88.5

88.5

88.5

88.5

83

83

45.5

45

67.5

92

92

155.5

76

25

25

25

25

25

30

30

45.5

92

67.5

45

92

76

155.5

45

89.5

67

44.5

91.5

75.5

155

K(Min)

25

25

25

25

25

30

30

A

B

C

E

D

F

G

K

J

+0.5

-0

+0.5

-0

H

7/10 page                                                                      KKAI208C01A-A1-20140904

Dimension

Panel size            

 

                             Size                     

  

            Hole size

2

.Alarm extension function table

0  
1  
2  

5

3  

AE1/AE2 value

Power 

alarm 

does not 

inhibit

Power

alarm 

inhibit

Alarm handling when show the HHH/LLL

Forced alarm output
Forced alarm close

Forced alarm output
Forced alarm close

Remark

As long as meet 

the requirement 

of alarm,

alarm output

Before the PV value 

reach the set value 

in the first time

,the alarm does not 

output.

The state when alarm keep HHH/LLL in previous time

The state when alarm keep HHH/LLL in previous time 

Operation of key function

 

1. Monitoring mode operation

      1

Under the measure mode,press“     ”into monitoring mode;and on the SV window sisplay“STP”.Press“    ”to back.

      2

It can alter SV value and switch operation event displaying STP.

      3

Under the monitoring mode,host control output will stop or set min output except alarm output and analog output.

 

2. PID Parameter identification and auto-tuning operation:

     1

The factory default PID parameters usually does not apply to use occasion;please using auto-tuning function to get a suitable PID parameter.

     2

The meter will enter control output since the power input, now,you can set the monitoring mode to avoid to affect the effect of auto-tuning 

          function,or switch off the power of control output load.No matter how to operate, it should guarantee the set value greater than the current measured value and 
         drop the bigger the better.
     3

In order to avoid the effect deu to alarm interlocking output,please set the proper alarm value,or remove the alarm effect.

     4

Set PID type and SV value;the factory default is PID with fuzzy.

     5

Set to PID control,please set the output to a proper range if it has OLL & OLH output limit;factory default is OLL=0%,OLH=100%

     6

Under the condition of PV value at normal room temperature,please back to monitoring mode or input the load power,and long press “AT” enter auto-tuning

mode,now,AT indicator will shine. 
     7

Auto-tuning will take the time,in order not to affect auto-tuning result,please don`t change the parameters or power-off.

     8

PID parameters will auto update when AT light is out and auto back auto-tuning mode.This monment,it will auto control exactly.

     9

It will abort the auto-tuning when you long press “AT”key,measure beyond the scope,display abnormally,swith to “STP”,power-off in the process of auto-tuning.

     10

NoteIn the place with output limit,it can`t get the best PID parameters event with the auto-tuning.

     11

You can set a proper PID parameter with your rich experience.

3.PID & Cooling control operation

     1

PID control act on host control output OUT1

Cooling control act on OUT2.

     2

AL1 alarm function & OUT2 can reuse,please set AD1 to 0 when using the cooling control;but the 1st alarm function can`t work after setting.

     3

Please set the control type OT to 3.

     4

Please set the cooling start offset to a value great than 5,to ensure the cooling would not affect the PID control impact.

     5

Please change the cooling control cycle to a proper value,and change the cooling scaling factor to a a proper value.

     6

When PV value > SV+DB value,the cooling control start to effect;the bigger value of PV,the longer output time of OUT2.

4.Signal linear auto-tuning function operation

     1

Set up the INP type,and ensure one of inputs(0

50mV

RT(0

400Ω)

4

20mA and 0

10V)

     2

Add the input signal to a proper input channel.

     3

Enter menu low-limit to calibrate CAL,press “AT”to flash”YES”;and set the input signal to min value and input to meter.

     4

When “YES”is flashing,and the min value of signal has input to meter,please press “SET”to ensure and save the calibrating value.

     5

After calibrating low-limit,enter the high limit to calibrate CAH in menu,and flash “YES”.

     6

Set the input signal to max value to meter,and press “SET”to ensure and save the calibrating value when the “YES”is flashing. 

     7

After calibrating,it can enter CAE,and change “N”to “Y”then it can use calibrating value,or it will use the factory default value.

     8

The linear signal value of high-limit input should not great than the inout standard value range ±10%.

     9

If you`re not satisfied with the calibrating result,you can reset.

R/S

R/S

Содержание AI208 Series

Страница 1: ...ault 10 Please tighten screw torque according to the rules If not it may lead to electric shock and fire 11 In order not to interfere with this products to dissipate heat please don t plug casing arou...

Страница 2: ...ted pair with a shield for remote RS485 communication cable and deal with the shield on the host side earth otherwise it will reduce the effect of noise filter 8 This product is not the fuse please se...

Страница 3: ...solation Note when there is no analog output communication port between and part of specification such as relay output is isolation SSR output is no isolation Name of universal panel R S Menu key ensu...

Страница 4: ...de and after power on long press SET key more than 3s to enter the menu parameters to ckeck the type b In the checking mode in menu you can press SET each short time to check the manu parameters recur...

Страница 5: ...nalog range low limit Analog range high limit note the value is reverse analog output when it less than analog range low limit Output low limit limit the output low limit current amplitude Setting val...

Страница 6: ...ose the function Temperature unit F Line signal input unit engineering work Digits User auto calibrating enable function this parameter is only for use of input signal expect TC RTD Y user of enable a...

Страница 7: ...normal room temperature please back to monitoring mode or input the load power and long press AT enter auto tuning mode now AT indicator will shine 7 Auto tuning will take the time in order not to af...

Страница 8: ...2 dyte seizes 2 data register The memory code of decimal integer 200 is 0x00C8 Note It should read DP value or ensure DP value in first to ensure the decimal point when reading data and need to transf...

Страница 9: ...ponse Write multi register CRC low CRC high Data high MeterADD StartADD Highbit StartADD Lowbit Databyte Length highbit Data byte Length high bit Databyte length FunctionID Data low CRCcode lowbit CRC...

Страница 10: ...DD ADD Communication baud rate BAD Communication relay setting DTC Optional input signal INP 1st loop alarm type AD1 2nd loop alarm type AD2 D7 D6 D5 D4 D3 D2 D1 D0 AT AL2 AL1 OUT2 OUT1 R Read R W Rea...

Отзывы: