AI208series temperature controller
2/10 page KKAI208C01A-A1-20140904
2
2
2
1
1
AI208-
□
-IRC18
AI208-
□
-ISC18
AI208-
□
-DC18
AI208-
□
-RB10
AI208-
□
-SB10
R
:
Relay output S:SSR output D:DC 4-20mA
(
set to analog output through ACT menu) K:SCR output(to be order)
I
:
4
~
20mA analog output (can adjust the current output through ACT menu
)
Blank
:
No
注
2.Cable caution
:
1
)
Please use specified compensation wire in the place of TC input;Please use insulated TC if the measured device is heated metal.
2
)
Please use the cable of lesser resistance in the place of RTD input,and the cable(3 wire) must be no resistance difference,but the total length is within 5m.
3
)
In order to avoid the effect of noise,please put the input dignal away from meter cable,power cable,load cable to wiring.
4
)
In order to reduce the power cables and the load power cables on the effect of this product,please use noise filter in the place where easy to effect.
You must install it on the grounding of the disk if you use the noise filter,and make the wiring to be shortest between noise filter output side and power connectors.
Don`t install fuse and switch on the wiring of noice filter output side,otherwise it will reduce the effect of noise filter.
5
)
It takes 5s from input power to output.If there is a place with interlocking actions circuit signal,please use timer relay.
6
)
Please use twisted pair with a shield for analog output line,and to ensure the reliabilty of signal,and connect Common mode choke on the front of sinal receiver to suppress
lines affected by interference if necessary,so that to
7
)
Please use twisted pair with a shield for remote RS485 communication cable,and deal with the shield on the host side earth,otherwise it will reduce the effect of noise filter.
8
)
This product is not the fuse;please set according to rated voltage 250V,rated current 1A if you need;fuse type:relay fuse.
9
)
Please use the suitable screw force and crimp terminal.
The screw terminal size
:
M3X8
(
with 6.8X6.8 square base
)
Recommended tightening torque
:
0.4N.m
Proper cables
:
0.25
~
1.65mm single cable/multiple core cable
10
)
Pla don`t put the Crimp terminal or bare wire part contact with adjacent connector.
Model Illustration
:
TE series is only one 4~20mA output function.For the size of 6
、
8
、
9,when relay output/SSR output is together with DC 4~20mA,it has discrimination with “I”;
for example:IR,IS,etc,but it has not this type model for the size of 4
、
7.
Please note the input signal type when you choose the model. 1st type:TC/RTD/mV/Rt;2nd type:mA/V
Ordering Information
Model
Control output
Alarm
Analog 4
~
20mA
RS485
Relay / 4
~
20mA
SSR / 4
~
20mA
4
~
20mA
Relay
Yes
Yes
No
No
Yes
Yes
Yes
No
No
SSR
multiplex with main control
□
:
Optional dimensions
Specifications
1
、
Electrical parameters
Communication port
Current output
SSR output
Environment
Sample rate
2SPS
Power supply
Power consumption
Relay capacity
Storage enenvironment
Insulation impedance
ESD
Pulse traip
anti-interference
Lightning surge
Frequency drop
Dielectric strength
Total weight
AC 250V /3A Life of rated load>10w times
AC/DC 100
~
240V
(
85-265V
)
< 6VA
Temperature of indoor
:
0
~
50
℃
no condensation
,
Humidity:
<
85%RH
,
altitude<2000m
-10
~
60
℃
,no condensation
DC 24V pulse level
,
load<30mA
DC 4
~
20mA load < 500Ω
,
Temperature drift 250PPM
RS485 port Modbus-RTU procotol,max input 30units
Input,output,power cabinet
>
20MΩ
IEC/EN61000-4-2 Contact ±4KV /Air ±8KV perf.Criteria B
IEC/EN61000-4-4 ±2KV perf.Criteria B
IEC/EN61000-4-5 ±2KV perf.Criteria B
IEC/EN61000-4-29 0%
~
70% perf.Criteria B
Signal input & output & power 1500VAC 1min
,
below 60V Low voltage circuit between DC500V,1min
About 400g