Note: If there is any change, please subject to the drawing on the meter

Methods of simple fault

Display

LLL/HHH

Methods

Checks whether the input disconnection and whether normal of FH value,FL value,working environment

temperature and whether collect of input signal.

Communication procotol

Meter use Modbus RTU to do RS485 half-duplex communication.Reading function ID:0x03,writing function ID:0x10/0x06.The meter use 16digits CRC to check

and will not feedback any information of checked error.

Data frame format:

1

Read register

Meter ADD

Function ID

Start ADD

High bit

Start ADD

Low bit

Data byte

Length/high bit

Data byte

Length/low bit

CRC code

low bit

CRC code

low bit

Host request

Read multi-register

For example:Host reads integer SV(set value 200

       The ADD code of SV is 0x2000

because SV is integer(2 dyte),seizes 2 data register.The memory code of decimal integer 200 is 0x00C8

Note:It should read DP value or ensure DP value in first to ensure the decimal point when reading data,and need to transform the reading data to get the actual value.

       Conversely,it should transform the data to corresponding ratio before writing the data in meter.

Start bit

Data bit

1

1                        2                              3                       4                            5                         6                            7                        8

0x01                     0x03                    0x20                    0x00                     0x00                    0x01                    0x8F                    0xCA

8

1

No

Stop bit

check bit

Handling of abnormal communication

If there is abnormal response

put the function ID on the top position 1.For example:Host request the function ID 0x03,and the function ID 0x84 will be back from host.

0x02---Illegal data reading location:data position of host beyond the address range of meter.

0x03---Illegal data writing location:writing data address of host beyond the writing address range of meter.
Communication cycle

Communication cycle is the time from host request to client back to data:communication cycle=time of time of client rtime of relay+time of back
Eg:9600 Baud rate:communication cycle of single measured data >250ms.

Содержание AI208 Series

Страница 1: ...ault 10 Please tighten screw torque according to the rules If not it may lead to electric shock and fire 11 In order not to interfere with this products to dissipate heat please don t plug casing arou...

Страница 2: ...ted pair with a shield for remote RS485 communication cable and deal with the shield on the host side earth otherwise it will reduce the effect of noise filter 8 This product is not the fuse please se...

Страница 3: ...solation Note when there is no analog output communication port between and part of specification such as relay output is isolation SSR output is no isolation Name of universal panel R S Menu key ensu...

Страница 4: ...de and after power on long press SET key more than 3s to enter the menu parameters to ckeck the type b In the checking mode in menu you can press SET each short time to check the manu parameters recur...

Страница 5: ...nalog range low limit Analog range high limit note the value is reverse analog output when it less than analog range low limit Output low limit limit the output low limit current amplitude Setting val...

Страница 6: ...ose the function Temperature unit F Line signal input unit engineering work Digits User auto calibrating enable function this parameter is only for use of input signal expect TC RTD Y user of enable a...

Страница 7: ...normal room temperature please back to monitoring mode or input the load power and long press AT enter auto tuning mode now AT indicator will shine 7 Auto tuning will take the time in order not to af...

Страница 8: ...2 dyte seizes 2 data register The memory code of decimal integer 200 is 0x00C8 Note It should read DP value or ensure DP value in first to ensure the decimal point when reading data and need to transf...

Страница 9: ...ponse Write multi register CRC low CRC high Data high MeterADD StartADD Highbit StartADD Lowbit Databyte Length highbit Data byte Length high bit Databyte length FunctionID Data low CRCcode lowbit CRC...

Страница 10: ...DD ADD Communication baud rate BAD Communication relay setting DTC Optional input signal INP 1st loop alarm type AD1 2nd loop alarm type AD2 D7 D6 D5 D4 D3 D2 D1 D0 AT AL2 AL1 OUT2 OUT1 R Read R W Rea...

Отзывы: