CP

CP1

PC

AL1

HY1

AD1

(1)

AL2

HY2
AD2

(1)

PS

INP

OT

LCK

ACT

FL

FH

BRL

BRH

OLL

OUT1 control cycle,1:SSR control output,4-200:relay control output.Unit:s

OUT2 control cycle,cooling relay output cycle.Unit:s

OUT2 cooling proportionality coefficient,the higher of value,the stronger of cooling
1st loop alarm value,note:the minus is dealed as absolute value when it is 

as a deviation value .

1st loop alarm backlash value

1st loop alarm type,note:the value should set 0 when 1st loop alarm is as OUT2;

Set AD2 to 0 when aetting value>6.Otherwise it will close alarm function when it is 0.
2nd loop alarm value,note:the minus is dealed as absolute value when it is as 

a deviation value .

2nd loop alarm backlash value

2nd loop alarm type,note:the value should set 0 to close alarm function when the AD1>6.
Translation correction value,display value=actual measured value+translation 

correction value

Optional input measured signal type:refer to input signal parameters table.

Note:it need to change the relevant parameters after changing.

Control type,0:ON/OFF control;1:PID control;2:compressor cooling control;

Lock function;0001:SV value can not be changed;0010:menu setting value only 

can check not change.

Control execution type,0:relay/SSR output;1:single SSR output control

(the product reserve)

2

4

20mA output controlplease set according selected meter  

3:TE4,TE7 can set 3and change 4-20mA to analog output. 
Measure range low limit,the setting value must be less than measure range high limit

Measure range high limit,the setting value must be more than measure range low limit.

Analog range low limit,note:the value is reverse analog output when it less than 

analog range low limit.
Analog range high limit,note:the value is reverse analog output when it less than 

analog range low limit.
Output low limit,limit the output low limit current amplitude.Setting value must be

 less than high limit setting

It can enter project menu with 0033 in the process of checking menu.

3:PID & cooling control,it should set the AD1 to 0,then OUT2 can operate.

1

200

4

200

1

100

FL

FH

0

1000

0

12

FL

FH

0

100

0

6

-199

999

0

10

0

3

0

999

0

2/0~3

Refer to measured 

signal parameter table

Refer to measured 

signal parameter table

moreFH

FL

FH

-5

100

20

20

10.0

200

1

1

600

1

2

0

0

1

0

0

-50

999

-50

999

0

6

SPD

Control speed fine tuning,optional 0(N)no function,1(slow),2(ss)medium fast,

3

SSS

very slow

4

F

fast

5

FF

 medium fast

6

FFF

express

0

6

7

OVS

Overshoot limit,in the process of PID control,when PV>SV+OVS,it force off output;
The lower value,the lower PID adjusted range,the worse control stability;please set 

a proper value according actual state.

0

999

5

N

8

DB

Bit control backlash(nagetive backlash bit control)or cooling control and compressor 

cooling control dead zone.
please change the value according to decimal position,when you change INP type.

0

100

10

28

29

30

31

32

OLH

BAD

ADD

DTC

FT

Output high limit,limit the output high limit current amplitude.Setting value must 

be more than low limit setting

RS485 communication baud rate 0

4.8

):

4800

1

9.6

):

9600

Communication ADD

Sequenced transport of communication data and setting 000 of respon relay;

1st is function reserve,2nd is byte.

PV filter coefficient of digital filter,the higher of value,the stronger of filter function

0

105

 0

4.8

, 1

9.6

0

255

Refer to communication 

procotol note

0

255

100

9.6

1

0

10

Sequenced exchange,3rd is respon relay,it can set 0~9 to 10~100ms.

5

D

Differential time,reduce the effect of differential time to a proper value,which can  

prevent the system oscillation.
The higher value,the stronger function of differential.Unit:s

0

999

30

Содержание AI208 Series

Страница 1: ...ault 10 Please tighten screw torque according to the rules If not it may lead to electric shock and fire 11 In order not to interfere with this products to dissipate heat please don t plug casing arou...

Страница 2: ...ted pair with a shield for remote RS485 communication cable and deal with the shield on the host side earth otherwise it will reduce the effect of noise filter 8 This product is not the fuse please se...

Страница 3: ...solation Note when there is no analog output communication port between and part of specification such as relay output is isolation SSR output is no isolation Name of universal panel R S Menu key ensu...

Страница 4: ...de and after power on long press SET key more than 3s to enter the menu parameters to ckeck the type b In the checking mode in menu you can press SET each short time to check the manu parameters recur...

Страница 5: ...nalog range low limit Analog range high limit note the value is reverse analog output when it less than analog range low limit Output low limit limit the output low limit current amplitude Setting val...

Страница 6: ...ose the function Temperature unit F Line signal input unit engineering work Digits User auto calibrating enable function this parameter is only for use of input signal expect TC RTD Y user of enable a...

Страница 7: ...normal room temperature please back to monitoring mode or input the load power and long press AT enter auto tuning mode now AT indicator will shine 7 Auto tuning will take the time in order not to af...

Страница 8: ...2 dyte seizes 2 data register The memory code of decimal integer 200 is 0x00C8 Note It should read DP value or ensure DP value in first to ensure the decimal point when reading data and need to transf...

Страница 9: ...ponse Write multi register CRC low CRC high Data high MeterADD StartADD Highbit StartADD Lowbit Databyte Length highbit Data byte Length high bit Databyte length FunctionID Data low CRCcode lowbit CRC...

Страница 10: ...DD ADD Communication baud rate BAD Communication relay setting DTC Optional input signal INP 1st loop alarm type AD1 2nd loop alarm type AD2 D7 D6 D5 D4 D3 D2 D1 D0 AT AL2 AL1 OUT2 OUT1 R Read R W Rea...

Отзывы: