![Toa VX-3308WM Скачать руководство пользователя страница 82](http://html.mh-extra.com/html/toa/vx-3308wm/vx-3308wm_operating-instructions-manual_1123506082.webp)
Chapter 3
OPERATION
3-
23
5.4. VX-3308WM's Operation Example
When the failure is detected, the built-in buzzer sounds, and the General fault indicator on the front panel
flashes.
VX-3308WM
Step 1.
Press the Fault ACK key to acknowledge the failure.
The buzzer stops sounding, and the General fault indicator switches from flashing to steady on.
Notes
• When the failure reception function has been assigned to the control input terminal on the rear panel
of the VX-3308WM, it is also possible to receive a system failure via control input. For details, see
the separate Setting Software Instructions, "EVENT SETTINGS."
• It is also possible to receive a system failure by shorting the Control input terminals on the rear panel
of the VX-3308WM.
Step 2.
Locate the cause, then remove it.
Connect a PC to the VX-3308WM and read out the log data using the VX-3000 Setting Software.
For details, see the separate Setting Software Instructions, "Maintenance."
Confirm the cause of failure or abnormality on the log data (in this example, the log data that the
speaker terminal for the zone 2F is open state is listed), then fix the fault part.
Note
Operation of failure indication differs depending on which the Failure indication setting is set to "Auto
reset" or "Manual reset" on the VX-3000 Setting Software.
[When set to "Auto reset"]
For most failure indications, the failure LED automatically goes off when the cause has been corrected.
For certain other failure indications, such as power amplifier failure or speaker shorts, the LED does
not automatically go off. In such cases, Fault reset key needs to be pressed.
[When set to "Manual reset"]
The failure indication is retained until the Failure reset key is pressed even when failure is restored.