![Toa VX-3308WM Скачать руководство пользователя страница 75](http://html.mh-extra.com/html/toa/vx-3308wm/vx-3308wm_operating-instructions-manual_1123506075.webp)
Chapter 3
OPERATION
3-
16
[Operation example 4 (Example of disablement of EMG control from CIN: Basic operation)]
You can stop the emergency activation from the control input when the system is in general mode.
This function is intended not to activate the emergency broadcast by the fire alarm system during maintenance.
Note
This function is enabled only when the system is in general mode. Even if you press the key to which this
function is assigned while the system is in emergency mode, a beep tone will sound, making the operation
invalid.
Step 1.
Press the "Disablement of EMG control from CIN" key
while the system is in general mode.
The key ON/OFF indicator lights green and the status
indicator of "disablement of EMG control from CIN"
function lights red.
In this condition, the emergency activation becomes
invalid even if the emergency broadcast pattern is
activated by way of the control input.
Step 2.
Press the "Disablement of EMG control from CIN" key
again.
The key ON/OFF indicator and the status indicator of
"disablement of EMG control from CIN" function go off.
Red Green
Status indicator of "disablement
of EMG control from CIN" function
Key ON/OFF indicator
"Disablement of EMG
Control from CIN" key
"Disablement of EMG
Control from CIN" key
[Operation example 5 (Example of disablement of EMG control from CIN: Operation when the function
is turned ON by other remote microphone)]
When the "Disablement of EMG control from CIN" key is assigned
to 2 or more remote microphones’ function keys, the buzzer will
sound and the status indicator of "disablement of EMG control
from CIN" function will flash red if this function is turned ON by
other remote microphone.
Status indicator of "disablement
of EMG control from CIN" function
Key ON/OFF indicator
"Disablement of EMG
Control from CIN" key
Step 1.
Press the "Disablement of EMG control from CIN" key
when the buzzer sounds.
The status indicator of "disablement of EMG controlfrom
CIN" function lights red.
Flashes red
Red
"Disablement of EMG
Control from CIN" key
Step 2.
Press the "Disablement of EMG control from CIN" key
again.
The key ON/OFF indicator lights green.
The status indicator of "disablement of EMG controlfrom
CIN" function remains lit red as long as this function is
kept ON by other remote microphone.
The status indicator of "disablement of EMG controlfrom
CIN" function goes off when the function is turned OFF
by all the remote microphones to which this function is
assigned.
Red Green
"Disablement of EMG
Control from CIN" key
Note
The emergency activation from the control input is kept invalid unless this function is turned OFF by all the
remote microphones to which this function is assigned.
9
9
9
9