![Toa VX-3308WM Скачать руководство пользователя страница 32](http://html.mh-extra.com/html/toa/vx-3308wm/vx-3308wm_operating-instructions-manual_1123506032.webp)
Chapter 2
INDICATOR STATUS OF REMOTE MICROPHONES
2-
19
1.19. Indicator State at the Time of Disablement of EMG Control from CIN
When the system is set to "Emergency," the "disablement of EMG control from CIN" function can be assigned
to the function key.
When this function is assigned to the function key, you can stop the emergency activation from the control input
when the system is in general mode.
This function is intended not to activate the emergency broadcast by the fire alarm system during maintenance.
When this function is assigned to 2 or more remote microphones, it can be made invalid only by performing
cancellation operation at all these remote microphones.
When this function is assigned to the function key, the 2 indicators next to the key indicate the key selection
status, enable/disable status of the function, and acknowledge status.
This function is enabled only when the system is in general mode. Even if you press the key to which this
function is assigned while the system is in emergency mode, a beep tone will sound, making the operation
invalid.
Notes
• For the emergency function settings, see the separate Setting Software Instructions, "BASIC SETTINGS."
• For instructions on assigning functions to the function key, see the separate Setting Software Instructions,
"EVENT SETTINGS."
Status indicator of "disablement of
EMG control from CIN" function
Key ON/OFF Indicator
Function key
("Disablement of EMG Control from CIN" key)
Indicator meanings are as follows:
Indicator
Status
Meaning
Key ON/OFF Indicator
Unlit
When the function key is not pressed
Lights green
When the function key is pressed
Status indicator of
"disablement of EMG
control from CIN" function
Unlit
When the disablement function of emergency activation from
the control input is set to OFF
Flashes red
When the disablement function of emergency activation from
the control input is turned ON by other remote microphone
Lights red
When the disablement function of emergency activation from
the control input is turned ON by this remote microphone
or when the status that this function is turned ON by other
remote microphone is acknowledged
Содержание VX-3308WM
Страница 5: ...Chapter 1 NOMENCLATURE ...
Страница 6: ...Chapter 1 NOMENCLATURE 1 2 1 Front VX 3308WM VOICE EVACUATION WALL MOUNT ...
Страница 14: ...Chapter 2 INDICATOR STATUS OF REMOTE MICROPHONES ...
Страница 60: ...Chapter 3 OPERATION ...