172-65627M-09 (SQ10) 18 Oct 2021
20
Parameter Settings Screen
Parameter Settings Screen (1)
No.
Function
Description
1
High Temp (
C)
Sets the temperature at which the high temperature alarm is
triggered.
・
Defined as: Input value + set temperature = high temperature
alarm value (When the temperature is set to 70
C and upper
limit alarm set temperature is set to 10
C, the high temperature
alarm value becomes 80
C.)
・
When the water temperature falls below the alarm value during
an active alarm, the unit will recover from the alarm status.
・
Factory setting: 10
C
2
High Temp
Alarm Delay
Sets the alarm delay time for the high temperature alarm.
・
When the water temperature exceeds the value set in No. 1
(High Temp) for a longer time period than set in No. 2, a high
temperature alarm will be triggered.
(When the high temperature alarm value is set to 80
C and
alarm delay is set to 10 seconds, an alarm will be triggered if
the water temperature exceeds 80
C for more than 10
seconds.)
・
When the temperature falls below the high temperature alarm
value within the set alarm delay time, an high temperature
alarm will not be triggered.
・
Factory setting: 10 seconds
3
Low Temp (
C)
Sets the temperature at which the low temperature alarm is
triggered.
・
Defined as: Set temperature
– input value = low temperature
alarm value.
(When the temperature is set to 70
C and the lower limit alarm
set temperature is set to 10
C, the low temperature alarm value
becomes 60
C.)
・
When the water temperature exceeds the alarm value during an
active alarm, the unit will recover from the alarm status.
・
Factory setting: 10
C
Continued on next page
8
5
6
7
1
2
3
4
9