172-65318MA-04 (GP10/GT10/GP14/GT14 PowerTrap) 23 Nov 2018
16
(2)
When flash steam is not involved
(For closed systems)
Determining the reservoir diameter and
length based on the amount of condensate:
Reservoir
Pi
Condensate
PowerTrap
Reservoir Table
(For equalized, closed system installations)
Amount of
Pumped
Medium
Reservoir Diameter (mm) & Length (m)
Amount of
Pumped
Medium
Reservoir Diameter (in) & Length (ft)
(kg/h)
40
50
80
100 150 200 250
(lb/h)
1½
2
3
4
6
8
10
300 or less 1.2m 0.7
500 or less 3.0 ft 2.0
400
1.5 1.0
700
4.0 2.5
1.0
500
2.0 1.2
0.5
1000
5.5 3.5
1.5
600
1.5
0.6
1200
4.5
2.0
1.0
800
2.0
0.8
0.5
1500
2.5
1.5
1000
1.0
0.7
2000
3.5
2.0
1500
1.5
1.0
3000
4.5
3.0
2000
2.0
1.3
0.6
4000
6.5
4.0
1.5
3000
2.0
0.9
0.5
5000
5.0
2.5
4000
1.2
0.7
6000
5.5
2.5
1.5
5000
1.4
0.8 0.5
7000
6.5
3.0
1.5
6000
1.7
1.0 0.6
8000
3.5
2.0
7000
2.0
1.2 0.7
9000
4.0
2.5
1.5
8000
1.3 0.8
10000
4.5
2.5
1.5
9000
1.5 0.9
12000
5.0
3.0
2.0
10000
1.7 1.0
14000
6.0
3.5
2.5
16000
6.5
4.0
2.5
18000
4.5
3.0
20000
1.5
1.5
NOTE: Reservoir length can be reduced by 50% when the motive pressure (Pm) divided by the
back pressure (P
b
) is "2" or greater. (When Pm ÷ P
b
≥
2)
(3)
When there are small quantities of flash steam and a large amount of condensate
(e.g., open systems pumping large amounts of super-cooled condensate)
Consult the sizing tables in sections (1) and (2).
Select the condensate receiver size based on the larger of (1) and (2)..
Select the vent pipe diameter and overflow pipe diameter from (1).