172-65318MA-04 (GP10/GT10/GP14/GT14 PowerTrap) 23 Nov 2018
15
Vented Receiver Table - 1
(For atmospheric, open system installations, applicable trap – GP10/GP14)
Flash Steam
up to ~
kg/h
Receiver Diameter
mm (in)
(Length: 1 m)
Vent Line
Diameter
mm (in)
Flash Steam
up to ~
lb/h
Receiver Diameter
in
(Length: 3.5 ft)
Vent Line
Diameter
in
25
80
(3)
25
(1)
50
3
1
50
100
(4)
50
(2)
75
4
1
1
/
2
75
125
(5)
50
(2)
100
4
2
100
150
(6)
80
(3)
200
6
2
1
/
2
150
200
(8)
80
(3)
300
8
3
200
200
(8)
100
(4)
400
8
4
300
250
(10)
125
(5)
600
10
4
400
300
(12)
125
(5)
800
12
6
500
350
(14)
150
(6)
1000
14
6
700
400
(16)
200
(8)
1400
16
8
800
450
(18)
200
(8)
1600
18
8
1000
500
(20)
200
(8)
2000
20
8
1100
500
(20)
250
(10)
2200
20
10
1400
550
(22)
250
(10)
2800
22
10
1500
600
(24)
250
(10)
3000
24
10
Vented Receiver Table - 2
(For atmospheric, open system installations, applicable trap – GP10/GP14)
Amount of
Condensate
kg/h
Receiver Diameter
mm (in)
(Length: 1 m)
Amount of
Condensate
lb/h
Receiver Diameter
in
(Length: 3.5 ft)
1000 or less
80
(3)
2200 or less
3
1500
100
(4)
3300
4
2000
125
(5)
4400
5
3000
150
(6)
6600
6
6000
200
(8)
13000
8
10000
250
(10)
22000
10
NOTE: When amount of flash steam and condensate are between two values in the table, select