172-65318MA-04 (GP10/GT10/GP14/GT14 PowerTrap) 23 Nov 2018
17
•
Installing Several PowerTrap
Units in Parallel
Refer to the figure below as a general guide for the piping when several PowerTrap units
are to be installed after the same pumped medium inlet pipe.
The size of the pumped medium inlet pipe, return line and exhaust pipe manifold is
determined by the number of PowerTrap units installed.
When specifications exist separately from the instruction manual, follow the
specifications.
Pumped Medium Return Line
P
um
p
ed M
edi
um
I
nl
et
P
ipe
Pumped Medium
E
x
haus
t P
ipe
F
ill
ing H
ead
A
Motive
Medium
Supply
O
v
er
fl
ow
P
ipe
Receiver
Medium Return
(Main Line)
V
ent
P
ipe
Exhaust Pipe Manifold
TLV
Power
Trap
E
x
haus
t P
ipe
E
x
haus
t P
ipe
Motive
Medium
Supply
Motive
Medium
Supply
TLV
Power
Trap
TLV
Power
Trap
NOTE: This sketch is for explanation purposes only and is not intended as an installation design.
Number of
PowerTrap
Units Installed
Pumped Medium
Inlet Pipe Size
Pumped
Medium Return
Line Size
Exhaust Pipe
Manifold Size
Overflow Pipe
Size
Vent Pipe Size
2
125 mm (5 in)
80 mm (3 in)
40 mm (1
1
/
2
in)
Determine
overflow pipe
size according
to “Sizing the
Condensate
Receiver/Reser
voir” on page 14
See the Vent
Line Diameter
column in
Table-1 on
page 15
3
150 mm (6 in)
100 mm (4 in)
50 mm (2 in)
4
200 mm (8 in)
100 mm (4 in)
65 mm (2
1
/
2
in)
5
200 mm (8 in)
125 mm (5 in)
65 mm (2
1
/
2
in)
6
200 mm (8 in)
125 mm (5 in)
80 mm (3 in)