Leak Test
Testing pressure for water pipe should be greater than 1.25 times the working pressure, and should not be less than
0.6MPa. Piping system is considered leak free if pressure drop is less than 0.02MPa after 5 minutes of pressure test.
Water pressure test should not be carried out at ambient temperature lower than 5˚C. Pressure gauge should be
well-calibrated with step precision of not less than 1.5; full scale value should be 1.5 to 2 times the biggest tested pressure reading.
During water leak test, water should be added gradually from lower side of the system until it reaches tested pressure.
Air vent should be purged to release trapped air. Stop water pump and inspect for pipe leakage. Do not repair leakage
under pressurized piping system.
Clean the piping system thoroughly after the water leak test (Equipment must be isolated), until the drained water is
free from dust, iron and other foreign particles.
Electrical Installation
Electrical installation should be done according to the local codes and regulations. Unit should be installed by qualified
personnel. Voltage tolerance should be kept at rated voltage ±10%. Phase imbalance must not be greater than 2%.
Communication bus between control modules and wired controllers shall use no less than 0.25mm2 Shielded Twisted Pair
cable size. Do not install data cable alongside the power cable, contactors, circuit breakers, inverters and etc to avoid
electromagnetic interference. Cable connections must be done using end connectors.
R
N
S
T
E
L3 N
L1L2
Q0
R
S
T
N
Power supply
to each module
Master
Slave #1
Slave #2
Busbar
Main power
supply
Busbar
Insulation
Copper strips
Cross sectional areal(A
x B)
Q1
Q2
Q3
Cross-sectional area of the busbar (AxB) should not smaller than cable size of the main power supply (in mm
2
). Refer to
the following table for minimal requirements of the wires:
Total running
current
Main power supply
cable size
Main power supply
cable size
Total running
current
A
mm
2
A
mm2
FCA201
45.0
16
45.0
16
FCA301
65.0
25
63.8
20
FCA202
85.0
25
90.0
35
301
105.0
35
108.8
35
FCA203
125.0
35
135.0
50
301
145.0
50
153.8
70
FCA204
165.0
50
180.0
70
301
185.0
70
198.8
95
FCA205
205.0
70
225.0
120
FCA206
245.0
95
270.0
150
FCA207
285.0
120
315.0
185
FCA208
325.0
150
360.0
240
FCA209
365.0
185
405.0
240
FCA210
405.0
240
450.0
300
FCA211
445.0
300
495.0
300
FCA212
485.0
300
540.0
400
303
545.0
400
596.4
400
306
605.0
400
652.8
400
309
665.0
400
709.2
400
FCA312
725.0
400
765.6
430
FCA - NC/NH
Model
FCA - EC/EH
Power Supply Cable For Each Module
Type of wire
R,S,T
N
Earth
Cable size (mm
2
)
Cable size (mm
2
)
FCA201
FCA301
FCA201
FCA301
16
25
16
20
10
10
10
10
10
10
10
10