Leak Test

Testing pressure for water pipe should be greater than 1.25 times the working pressure, and should not be less than 

0.6MPa. Piping system is considered leak free if pressure drop is less than 0.02MPa after 5 minutes of pressure test.

Water  pressure  test  should  not  be  carried  out  at  ambient  temperature  lower  than  5˚C.  Pressure  gauge  should  be

 

well-calibrated with step precision of not less than 1.5; full scale value should be 1.5 to 2 times the biggest tested pressure reading.
During water leak test, water should be added gradually from lower side of the system until it reaches tested pressure. 

Air vent should be purged to release trapped air. Stop water pump and inspect for pipe leakage. Do not repair leakage 

under pressurized piping system. 
Clean the piping system thoroughly after the water leak test (Equipment must be isolated), until the drained water is 

free from dust, iron and other foreign particles.

Electrical Installation

Electrical installation should be done according to the local codes and regulations. Unit should be installed by qualified 

personnel. Voltage tolerance should be kept at rated voltage ±10%. Phase imbalance must not be greater than 2%. 

Communication bus between control modules and wired controllers shall use no less than 0.25mm2 Shielded Twisted Pair 

cable size. Do not install data cable alongside the power cable, contactors, circuit breakers, inverters and etc to avoid 

electromagnetic interference. Cable connections must be done using end connectors.

R

N

S
T

E

L3 N

L1L2

Q0

R

S

T

N

Power supply

to each module

Master

Slave #1

Slave #2

Busbar

Main power

supply

Busbar

Insulation

Copper strips

Cross sectional areal(A 

x B)

Q1

Q2

Q3

Cross-sectional area of the busbar (AxB) should not smaller than cable size of the main power supply (in mm

2

). Refer to 

the following table for minimal requirements of the wires:

Total running

current

Main power supply

cable size 

Main power supply

cable size 

Total running

current

A

mm

2

A

mm2

FCA201

45.0

16

45.0

16

FCA301

65.0

25

63.8

20

FCA202

85.0

25

90.0

35

301

105.0

35

108.8

35

FCA203

125.0

35

135.0

50

301

145.0

50

153.8

70

FCA204

165.0

50

180.0

70

301

185.0

70

198.8

95

FCA205

205.0

70

225.0

120

FCA206

245.0

95

270.0

150

FCA207

285.0

120

315.0

185

FCA208

325.0

150

360.0

240

FCA209

365.0

185

405.0

240

FCA210

405.0

240

450.0

300

FCA211

445.0

300

495.0

300

FCA212

485.0

300

540.0

400

303

545.0

400

596.4

400

306

605.0

400

652.8

400

309

665.0

400

709.2

400

FCA312

725.0

400

765.6

430

FCA - NC/NH

Model

FCA - EC/EH

Power Supply Cable For Each Module

Type of wire

R,S,T

N

Earth

 

Cable size (mm

2

Cable size (mm

2

)

 

FCA201 

FCA301 

FCA201 

FCA301

 

16 

25 

16 

20

 

10 

10 

10 

10

 

10 

10 

10 

10

Содержание FCA 201 EC

Страница 1: ...Installation Operation Maintenance Manual AIR COOLED MODULAR CHILLER Chiller Products FCHI01 00...

Страница 2: ...nd Clearance 8 Lifting 8 Water System Installation 11 Electrical Installation 12 Commissioning 23 Pre Start Checklist 23 Startup Procedure Servicing and Maintenance 24 Troubleshooting 25 Contents AIR...

Страница 3: ...ponents to perform these tasks Electrical wiring must not be physically in contact with refrigerant piping compressor or any moving parts of the fan motors Caution Avoid direct contact with sharp edge...

Страница 4: ...Page 3 Dimensions Model FCA 201 301 EC EH A B FCA201 EC EH 1030 515 FCA301 EC EH 1073 536 5 Water Inlet Water Outlet Dimensions in mm Model FCA 201 301 NC NH Water Inlet Water Outlet Dimensions in mm...

Страница 5: ...nt space must be allocated for water drainage ventilation and service Main water supply and return should be located at least 1 meter away from the unit for maintenance Proper water drainage should be...

Страница 6: ...and ensure good unit performance reduce the usage of U bends and vertical piping Please refer to the following diagram and instructions for proper piping installation FCA 201 301 EC EH Balancing Valve...

Страница 7: ...gy for optimum cooling heating unit capacity Leak test should be carried out and water pipes should be cleaned before piping is insulated and water is supplied to chiller unit Cooling Heating Capacity...

Страница 8: ...shall use no less than 0 25mm2 Shielded Twisted Pair cable size Do not install data cable alongside the power cable contactors circuit breakers inverters and etc to avoid electromagnetic interference...

Страница 9: ...erature sensor Circuit 2 condenser temperature sensor Circuit 1 condenser temperature sensor To next module Remove ON OFF GND 12V A B External interlock Operation indicator External alarm Transformer...

Страница 10: ...se High pressure switch Low pressure switch Overload protection Main switch Water flow switch Discharge temperature switch Last module close Jumper setting Overload protection setting 1 Field wiring F...

Страница 11: ...Overload protection Main switch Water flow switch Discharge temperature switch 4 way valve Crankcase heater 4WV1 2 CCH LPH1 2 Low pressure switch heating Transformer FCA201EH FCA201NH Last module clo...

Страница 12: ...ater flow switch Discharge temperature switch 4 way valve Crankcase heater 4WV1 2 CCH LPH1 2 Low pressure switch heating FCA201EH FCA201NH Last module close Jumper setting Overload protection setting...

Страница 13: ...nal interlock Operation indicator External alarm Transformer GND 12V A B Discharge temperature switch Last module close Jumper setting FCA301EC FCA301NC Overload protection setting DIP switch setting...

Страница 14: ...on Compressor Fan motor Power indicator Contactor Phase protector Fuse Timer Discharge temperature switch Last module close Jumper setting FCA301EC FCA301NC Overload protection setting Timer setting F...

Страница 15: ...Fuse Timer Discharge temperature switch Last module close Jumper setting FCA301EC FCA301NC Overload protection setting Timer setting FCA301EC FCA301NC 8S 8S DIP switch setting DIP S2 FCA301EC FCA301NC...

Страница 16: ...r External alarm Transformer Discharge temperature switch Last module close Jumper setting FCA301EH FCA301NH Overload protection setting Timer setting FCA301EH FCA301NH 8S 8S DIP switch setting DIP S2...

Страница 17: ...indicator Contactor Phase protector Fuse 4 way valve Crankcase heater Timer Discharge temperature switch Operation indicator External alarm Last module close Jumper setting FCA301EH FCA301NH Overload...

Страница 18: ...sor To next module From previous module Operation indicator External alarm Last module close Jumper setting FCA301EH FCA301NH Overload protection setting Timer setting FCA301EH FCA301NH 8S 8S 1 Field...

Страница 19: ...scription OUT1 Water pump OUT2 Condenser fan 1 OUT3 Liquid valve 1 OUT4 Compressor 1 OUT5 4 way valve 1 OUT6 Auxiliary heater OUT7 Condenser fan 2 OUT8 Liquid valve 2 OUT9 Compressor 2 OUT10 4 way val...

Страница 20: ...Date settings MENU Sub menu Item selection TIME Time settings DISPLAY To select water temperature display ENTER Execute instruction SET To change parameter settings CANCEL Clear instruction CLEAR To...

Страница 21: ...ress and hold key simultaneously for 5 seconds to toggle it ON or OFF Error codes display area will show to indicate key lock is activated When the key lock is activated only the key is functioning as...

Страница 22: ...C 1 C 5 C 13 Heating sensor select In Entering water Ou Leaving water In In Ou j Last State Memory To set and activate last state memory press MENU key then press SET key simultaneously for 5 seconds...

Страница 23: ...er temperature 1 55 C Heat mode only 13 Circuit 1 condenser temperature sensor TH1 error Outdoor coil sensor open short 14 Water temperature sensor TH3 error Water temperature sensor TH3 open short 15...

Страница 24: ...led wiring is according to manufacturer s wiring diagram 3 Unit s power supply and controls are properly connected and unit is properly GROUNDED 4 Temperature sensor on main water supply and return in...

Страница 25: ...gerant system if pressure drop occurs Service And Maintenance Evaporator The construction of the evaporator does not allow it to be cleaned mechanically However chemical cleaning should be adopted by...

Страница 26: ...y Wrong TXV setting Strainer choked Low refrigerant flow Water system choked air trap Refrigerant over charged Ambient temperauture too high Un condensable gas exist in the circuit example air Condens...

Страница 27: ...Installation Operation Maintenance Manual AIR COOLED MODULAR CHILLER Chiller Products FCHI01 00...

Отзывы: