4)  Functions

 

a)  ON/OFF

 

 

Press 

 key to switch ON/OFF the system.

 

b)  Date/Time Setting

To  set  clock,  press  <SET>  key  to  enter  time  setting  menu,  “Time  display  area”  will  show  “SET  CLOCK”  to

 

indicate time setting mode. Press <TIME +/-> key to change the minute value and hold the <SET> key to 

change the hour value. Press <SET> key again to enter date setting menu, “Time display area” will show “SET 

DAY” to indicate date setting mode, press <DAY> key to set day value.

 

c)  7 days ON/OFF TIMER

To set 7 days ON timer, press <TIMER> key from main menu to enter timer setting menu, “ON TIMER” and “OFF 

TIMER” will blink to indicate timer setting menu. Press <TIMER> key again, “ON TIMER” will blink to indicate ON 

timer setting is activated. If there is no pervious setting of ON timer for that particular day, “Time display area” 

will show “-:--“, otherwise, the “Timer display area” will show the previously set ON timer. Press <DAY> key to 

set day value. Press <TIME +/-> key to change the minute and hour value. 

To  clear  the  entire  ON  timer  (OFF  timer)  setting,  activate  the  ON  timer  (OFF  timer)  menu,  press  and  hold

 

<CANCEL> key for 5 seconds.

Note: If there is unimplemented timer for that particular day, the “Timer display area” will show “ON TIMER” or 

“OFF TIMER”.

 

d)  Manual Defrost

To execute manual defrost, press and hold <DEF> key for 5 seconds to enter manual defrost menu, “Error codes 

display area” will show “Hd” with a long beep sound to indicate manual defrost menu. “Address display area” 

will show the particular circuit, e.g. circuit #6 means 2nd refrigerant circuit for module #3. “Time display area”

 

will show the defrost interval time. Press <MENU +/-> key to select the circuit number. Press 

+

-

 key to 

change the defrost interval time (30 ~ 240 sec). Press <ENTER> key to accept the selection or press <CANCEL> 

key to reject selection and exit.

e)  Key Lock

 

To  prevent  unauthorized  and  accidental  setting  of  control,  the  system  comes  with  Key    Lock  function.  To

 

activate Key Lock, press and hold 

+

-

 key simultaneously for 5 seconds to toggle it ON or OFF. “Error codes 

display area” will show   to indicate key lock is activated. When the key lock is activated, only the 

 key is 

functioning as normal.

f)  Water Temperature Display - Chiller

 

To  monitor  the  entering  or  leaving  water  temperature,  press  <DISPLAY>  key  to  select  entering  water  or 

leaving  water  temperature.  “Temperature  display  area”  will  show  “INLET  TEMP”  to  indicate  entering  water

 

temperature display, otherwise, “INLET TEMP” indicator is OFF to indicate leaving water temperature. Press and 

hold <DISPLAY> for 1 sec to enter ambient temperature menu, the “Temperature display area” will blink to 

indicate ambient temperature. Press <DISPLAY> key again to exit the ambient temperature menu.

g)  Water Temperature Display - Module

 

To  monitor  the  leaving  water  temperature  for  each  circuit  of  the  module,  press  <MENU  +>  key  then  press 

<DISPLAY>  key  simultaneously  for  5  seconds.  “Error  codes  display  area”  will  show  “L1”  with  a  long  beep 

sound to indicate water temperature display. “Address display area” will show module address. Indicator 

 

means circuit #1 and 

 means circuit #2. For example, L1 02 

 means leaving water temperature for 

circuit #1 of module #2 will be shown on the “Temperature display area”. Press the following key to change the

 

display parameters:

a.  Press <MENU +/-> key to select particular module.

b.  Press <DISPLAY> key to select circuit #1 or circuit #2.

c.  Press <CANCEL> to exit.

h)  Condenser Temperature Display - module

 

To  monitor  the  condenser  temperature  for  each  module,  press  <MENU  ->  key  then  press  <DISPLAY>  key

 

simultaneously  for  5  seconds.  “Error  code  display  area”  will  show  “L2”  with  a  long  beep  sound  to  indicate

 

condenser  temperature  display.  “Address  Display  Area”  will  show  the  module  address.  Indicator 

  means 

circuit #1 and 

 means circuit #2 of each module. For example, L2 02 

 means condenser temperature for 

circuit #1 of module #2 will be shown on the “Temperature display area”. Press the following key to change the 

display parameters:

 

 

a. 

Press <MENU +/-> key to select particular module.

 

 

b.  Press <DISPLAY> key to select circuit #1 or circuit #2.

 

 

c. 

Press <CANCEL> to exit.

 

Содержание FCA 201 EC

Страница 1: ...Installation Operation Maintenance Manual AIR COOLED MODULAR CHILLER Chiller Products FCHI01 00...

Страница 2: ...nd Clearance 8 Lifting 8 Water System Installation 11 Electrical Installation 12 Commissioning 23 Pre Start Checklist 23 Startup Procedure Servicing and Maintenance 24 Troubleshooting 25 Contents AIR...

Страница 3: ...ponents to perform these tasks Electrical wiring must not be physically in contact with refrigerant piping compressor or any moving parts of the fan motors Caution Avoid direct contact with sharp edge...

Страница 4: ...Page 3 Dimensions Model FCA 201 301 EC EH A B FCA201 EC EH 1030 515 FCA301 EC EH 1073 536 5 Water Inlet Water Outlet Dimensions in mm Model FCA 201 301 NC NH Water Inlet Water Outlet Dimensions in mm...

Страница 5: ...nt space must be allocated for water drainage ventilation and service Main water supply and return should be located at least 1 meter away from the unit for maintenance Proper water drainage should be...

Страница 6: ...and ensure good unit performance reduce the usage of U bends and vertical piping Please refer to the following diagram and instructions for proper piping installation FCA 201 301 EC EH Balancing Valve...

Страница 7: ...gy for optimum cooling heating unit capacity Leak test should be carried out and water pipes should be cleaned before piping is insulated and water is supplied to chiller unit Cooling Heating Capacity...

Страница 8: ...shall use no less than 0 25mm2 Shielded Twisted Pair cable size Do not install data cable alongside the power cable contactors circuit breakers inverters and etc to avoid electromagnetic interference...

Страница 9: ...erature sensor Circuit 2 condenser temperature sensor Circuit 1 condenser temperature sensor To next module Remove ON OFF GND 12V A B External interlock Operation indicator External alarm Transformer...

Страница 10: ...se High pressure switch Low pressure switch Overload protection Main switch Water flow switch Discharge temperature switch Last module close Jumper setting Overload protection setting 1 Field wiring F...

Страница 11: ...Overload protection Main switch Water flow switch Discharge temperature switch 4 way valve Crankcase heater 4WV1 2 CCH LPH1 2 Low pressure switch heating Transformer FCA201EH FCA201NH Last module clo...

Страница 12: ...ater flow switch Discharge temperature switch 4 way valve Crankcase heater 4WV1 2 CCH LPH1 2 Low pressure switch heating FCA201EH FCA201NH Last module close Jumper setting Overload protection setting...

Страница 13: ...nal interlock Operation indicator External alarm Transformer GND 12V A B Discharge temperature switch Last module close Jumper setting FCA301EC FCA301NC Overload protection setting DIP switch setting...

Страница 14: ...on Compressor Fan motor Power indicator Contactor Phase protector Fuse Timer Discharge temperature switch Last module close Jumper setting FCA301EC FCA301NC Overload protection setting Timer setting F...

Страница 15: ...Fuse Timer Discharge temperature switch Last module close Jumper setting FCA301EC FCA301NC Overload protection setting Timer setting FCA301EC FCA301NC 8S 8S DIP switch setting DIP S2 FCA301EC FCA301NC...

Страница 16: ...r External alarm Transformer Discharge temperature switch Last module close Jumper setting FCA301EH FCA301NH Overload protection setting Timer setting FCA301EH FCA301NH 8S 8S DIP switch setting DIP S2...

Страница 17: ...indicator Contactor Phase protector Fuse 4 way valve Crankcase heater Timer Discharge temperature switch Operation indicator External alarm Last module close Jumper setting FCA301EH FCA301NH Overload...

Страница 18: ...sor To next module From previous module Operation indicator External alarm Last module close Jumper setting FCA301EH FCA301NH Overload protection setting Timer setting FCA301EH FCA301NH 8S 8S 1 Field...

Страница 19: ...scription OUT1 Water pump OUT2 Condenser fan 1 OUT3 Liquid valve 1 OUT4 Compressor 1 OUT5 4 way valve 1 OUT6 Auxiliary heater OUT7 Condenser fan 2 OUT8 Liquid valve 2 OUT9 Compressor 2 OUT10 4 way val...

Страница 20: ...Date settings MENU Sub menu Item selection TIME Time settings DISPLAY To select water temperature display ENTER Execute instruction SET To change parameter settings CANCEL Clear instruction CLEAR To...

Страница 21: ...ress and hold key simultaneously for 5 seconds to toggle it ON or OFF Error codes display area will show to indicate key lock is activated When the key lock is activated only the key is functioning as...

Страница 22: ...C 1 C 5 C 13 Heating sensor select In Entering water Ou Leaving water In In Ou j Last State Memory To set and activate last state memory press MENU key then press SET key simultaneously for 5 seconds...

Страница 23: ...er temperature 1 55 C Heat mode only 13 Circuit 1 condenser temperature sensor TH1 error Outdoor coil sensor open short 14 Water temperature sensor TH3 error Water temperature sensor TH3 open short 15...

Страница 24: ...led wiring is according to manufacturer s wiring diagram 3 Unit s power supply and controls are properly connected and unit is properly GROUNDED 4 Temperature sensor on main water supply and return in...

Страница 25: ...gerant system if pressure drop occurs Service And Maintenance Evaporator The construction of the evaporator does not allow it to be cleaned mechanically However chemical cleaning should be adopted by...

Страница 26: ...y Wrong TXV setting Strainer choked Low refrigerant flow Water system choked air trap Refrigerant over charged Ambient temperauture too high Un condensable gas exist in the circuit example air Condens...

Страница 27: ...Installation Operation Maintenance Manual AIR COOLED MODULAR CHILLER Chiller Products FCHI01 00...