Control Module Setting and Description

a)  Input Signal

Input Signal

Description

Type of control

IN_1

Flow switch

NC

IN_2

Cooling low pressure #1

NC

IN_3

High pressure #1

NC

IN_4

Compressor #1 overload

NC

IN_5

Heating low pressure #1

NC

IN_6

Power supply or phase failure

NC

IN_7

Cooling low pressure #2

NC

IN_8

High pressure #2

NC

IN_9

Compressor #2 overload

NC

IN_10

Heating low pressure #2

NC

IN_11

External interlock

NC

IN_12

Remote ON/OFF

Close = ON; Open = OFF

TH1

Outdoor Coil temperature 1

NTC

TH2

Outdoor Coil temperature 2

NTC

TH3

Chiller leaving water temperature #1

NTC

TH4

Chiller leaving water temperature #2

NTC

TH5

System leaving water temperature

NTC

TH6

System entering water temperature

NTC

TH7

Ambient temperature

NTC

b)  Output Signal

Output Signal

Description

OUT1

Water pump

OUT2

Condenser fan #1

OUT3

Liquid valve #1

OUT4

Compressor #1

OUT5

4 way valve #1

OUT6

Auxiliary heater

OUT7

Condenser fan #2

OUT8

Liquid valve #2

OUT9

Compressor #2

OUT10

4 way valve #2

OUT11

Operation indicator

AL_IN

AL_OUT

External alarm

c)  Address Setting (DIP S1.1 - S1.4)

S1.1

S1.2

S1.3

S1.4

Add

OFF

OFF

OFF

OFF

1

ON

OFF

OFF

OFF

2

OFF

ON

OFF

OFF

3

ON

ON

OFF

OFF

4

OFF

OFF

ON

OFF

5

ON

OFF

ON

OFF

6

OFF

ON

ON

OFF

7

ON

ON

ON

OFF

8

OFF

OFF

OFF

ON

9

ON

OFF

OFF

ON

10

OFF

ON

OFF

ON

11

ON

ON

OFF

ON

12

d)  Chiller Setting (DIP S2.5 – S2.8)

S2.5

S2.6

S2.7

S2.8

Model

OFF

ON

OFF

OFF

FCA201EC/EH/ECA both individual and group control.

ON

ON

OFF

OFF

FCA201NC/NH both individual and group control.

OFF

OFF

OFF

OFF

FCA201FH both individual and group control.

OFF

ON

ON

OFF

FCA301EC/EH individual control only.

OFF

ON

OFF

OFF

FCA301EC/EH group control (Master/Slave).

ON

ON

ON

OFF

FCA301NC/NH individual control only.

ON

ON

OFF

OFF

FCA301NC/NH group control (Master/Slave).

Содержание FCA 201 EC

Страница 1: ...Installation Operation Maintenance Manual AIR COOLED MODULAR CHILLER Chiller Products FCHI01 00...

Страница 2: ...nd Clearance 8 Lifting 8 Water System Installation 11 Electrical Installation 12 Commissioning 23 Pre Start Checklist 23 Startup Procedure Servicing and Maintenance 24 Troubleshooting 25 Contents AIR...

Страница 3: ...ponents to perform these tasks Electrical wiring must not be physically in contact with refrigerant piping compressor or any moving parts of the fan motors Caution Avoid direct contact with sharp edge...

Страница 4: ...Page 3 Dimensions Model FCA 201 301 EC EH A B FCA201 EC EH 1030 515 FCA301 EC EH 1073 536 5 Water Inlet Water Outlet Dimensions in mm Model FCA 201 301 NC NH Water Inlet Water Outlet Dimensions in mm...

Страница 5: ...nt space must be allocated for water drainage ventilation and service Main water supply and return should be located at least 1 meter away from the unit for maintenance Proper water drainage should be...

Страница 6: ...and ensure good unit performance reduce the usage of U bends and vertical piping Please refer to the following diagram and instructions for proper piping installation FCA 201 301 EC EH Balancing Valve...

Страница 7: ...gy for optimum cooling heating unit capacity Leak test should be carried out and water pipes should be cleaned before piping is insulated and water is supplied to chiller unit Cooling Heating Capacity...

Страница 8: ...shall use no less than 0 25mm2 Shielded Twisted Pair cable size Do not install data cable alongside the power cable contactors circuit breakers inverters and etc to avoid electromagnetic interference...

Страница 9: ...erature sensor Circuit 2 condenser temperature sensor Circuit 1 condenser temperature sensor To next module Remove ON OFF GND 12V A B External interlock Operation indicator External alarm Transformer...

Страница 10: ...se High pressure switch Low pressure switch Overload protection Main switch Water flow switch Discharge temperature switch Last module close Jumper setting Overload protection setting 1 Field wiring F...

Страница 11: ...Overload protection Main switch Water flow switch Discharge temperature switch 4 way valve Crankcase heater 4WV1 2 CCH LPH1 2 Low pressure switch heating Transformer FCA201EH FCA201NH Last module clo...

Страница 12: ...ater flow switch Discharge temperature switch 4 way valve Crankcase heater 4WV1 2 CCH LPH1 2 Low pressure switch heating FCA201EH FCA201NH Last module close Jumper setting Overload protection setting...

Страница 13: ...nal interlock Operation indicator External alarm Transformer GND 12V A B Discharge temperature switch Last module close Jumper setting FCA301EC FCA301NC Overload protection setting DIP switch setting...

Страница 14: ...on Compressor Fan motor Power indicator Contactor Phase protector Fuse Timer Discharge temperature switch Last module close Jumper setting FCA301EC FCA301NC Overload protection setting Timer setting F...

Страница 15: ...Fuse Timer Discharge temperature switch Last module close Jumper setting FCA301EC FCA301NC Overload protection setting Timer setting FCA301EC FCA301NC 8S 8S DIP switch setting DIP S2 FCA301EC FCA301NC...

Страница 16: ...r External alarm Transformer Discharge temperature switch Last module close Jumper setting FCA301EH FCA301NH Overload protection setting Timer setting FCA301EH FCA301NH 8S 8S DIP switch setting DIP S2...

Страница 17: ...indicator Contactor Phase protector Fuse 4 way valve Crankcase heater Timer Discharge temperature switch Operation indicator External alarm Last module close Jumper setting FCA301EH FCA301NH Overload...

Страница 18: ...sor To next module From previous module Operation indicator External alarm Last module close Jumper setting FCA301EH FCA301NH Overload protection setting Timer setting FCA301EH FCA301NH 8S 8S 1 Field...

Страница 19: ...scription OUT1 Water pump OUT2 Condenser fan 1 OUT3 Liquid valve 1 OUT4 Compressor 1 OUT5 4 way valve 1 OUT6 Auxiliary heater OUT7 Condenser fan 2 OUT8 Liquid valve 2 OUT9 Compressor 2 OUT10 4 way val...

Страница 20: ...Date settings MENU Sub menu Item selection TIME Time settings DISPLAY To select water temperature display ENTER Execute instruction SET To change parameter settings CANCEL Clear instruction CLEAR To...

Страница 21: ...ress and hold key simultaneously for 5 seconds to toggle it ON or OFF Error codes display area will show to indicate key lock is activated When the key lock is activated only the key is functioning as...

Страница 22: ...C 1 C 5 C 13 Heating sensor select In Entering water Ou Leaving water In In Ou j Last State Memory To set and activate last state memory press MENU key then press SET key simultaneously for 5 seconds...

Страница 23: ...er temperature 1 55 C Heat mode only 13 Circuit 1 condenser temperature sensor TH1 error Outdoor coil sensor open short 14 Water temperature sensor TH3 error Water temperature sensor TH3 open short 15...

Страница 24: ...led wiring is according to manufacturer s wiring diagram 3 Unit s power supply and controls are properly connected and unit is properly GROUNDED 4 Temperature sensor on main water supply and return in...

Страница 25: ...gerant system if pressure drop occurs Service And Maintenance Evaporator The construction of the evaporator does not allow it to be cleaned mechanically However chemical cleaning should be adopted by...

Страница 26: ...y Wrong TXV setting Strainer choked Low refrigerant flow Water system choked air trap Refrigerant over charged Ambient temperauture too high Un condensable gas exist in the circuit example air Condens...

Страница 27: ...Installation Operation Maintenance Manual AIR COOLED MODULAR CHILLER Chiller Products FCHI01 00...

Отзывы: