2.
Install male
1
/
2
” flare union adapter to
1
/
2
” NPT internal thread elbow at inlet of
regulator. On models equipped with standard twin burners, install the male pipe
thread end of the
1
/
2
” flare union adapter to the
1
/
2
” NPT internal thread at inlet of
pressure regulator. Use a wrench on the regulator fitting to avoid damage.
3.
Install male
1
/
2
” or
3
/
4
” flare union adapter to the NPT internal thread of the
manual shut-off valve, taking care to secure the shut-off valve to keep it from
turning.
4.
The gas supply pressure for checking the regulator setting is 7 in.w.c. (Nature Gas)
and 11 inch.w.c. (LP gas) connect flexible gas line connector to the regulator on the
range. Position range to permit connection at the shut-off valve.
5.When all connections have been made, make sure all range controls are in the position and
turn on main gas supply valve.
6.Leak testing of the appliance shall be conducted according
to the manufacture’s instructions.
Use some soap water (50% water and 50% soap) or a leak detector at all joints and connections
to check for leaks in the system. Do not use a flame to check for gas leaks.
7.The appliance must be isolated from the buildi
ng’s gas supply piping system by closing its
individual manual shut-off valve during any pressure testing of the gas supply piping system at
test pressure equal to or less than 1/2 psig(3.5kPa).
After installation:
Check ignition of cooktop burners.
Check ignition of oven burner.
Visually check tubular burner (oven burner) re-ignition to be sure both rows of burner ports are
relighting each time.