MEC 310 GENSET CONTROLLER
PM075 REV 2 09/08/20
Page 66
THOMSON TECHNOLOGY
AMF test function (A dependent)
When the AMF test is initiated, the MEC 310 will go through the AMF sequence and run the engine
for the time set in parameter 7040. In this parameter it is also selected if this sequence should be
started by a digital input and/or the test push-button on the front of the MEC 310. If the timer is set
to 0, the test sequence will be interrupted when the digital input or test push-button is deactivated.
This means that digital input can be used to activate and deactivate the test sequence. When the
timer runs out or the input is deactivated (timer set to 0), the mains restore sequence and the stop
sequence including cooling down will be carried out.