
MEC 310 GENSET CONTROLLER
PM075 REV 2 09/08/20
Page 55
THOMSON TECHNOLOGY
The TSP 300 software setting looks like this:
VDO input 2, oil pressure
VDO sensor type
Pressure
Type 1
Type 2
Type 3
Bar
Psi
Ω
Ω
Ω
0
0
10.0
10.0
Configurable
0.5
7
27.2
1.0
15
44.9
1.5
22
62.9
2.0
29
81.0
51.5
2.5
36
99.2
3.0
44
117.1
71.0
3.5
51
134.7
4.0
58
151.9
89.6
4.5
65
168.3
5.0
73
184.0
107.3
6.0
87
124.3
7.0
102
8.0
116
155.7
9.0
131
10.0
145
184.0
Type 4 is fully configurable with 8 points in the range 0-240
Ω
and 0-10.0 bar.
The
parameter settings can be found from menu 10810.
8 settings are available from 0-150%.
Содержание MEC 310 - APLLICATION NOTES EXTERNAL I-O MODULES
Страница 2: ...This description of options covers the following products MEC 310 SW version 1 2X X...
Страница 27: ...MEC 310 GENSET CONTROLLER PM075 REV 2 09 08 20 Page 23 THOMSON TECHNOLOGY Unit dimensions and panel cutout...
Страница 57: ...MEC 310 GENSET CONTROLLER PM075 REV 2 09 08 20 Page 53 THOMSON TECHNOLOGY 8 15 display views are empty...