MEC 310 GENSET CONTROLLER
PM075 REV 2 09/08/20
Page 96
THOMSON TECHNOLOGY
Analogue inputs 0(4)-20mA
The scaling of the 0(4)-20mA inputs for correct display reading can only be done via the TPS 300
software.
4120 0-20 4-20mA 1.1
No.
Setting
Min. setting
Max. setting
Factory
setting
4121
0(4)-20mA 1.1
Set point
4mA
20mA
10mA
4122
0(4)-20mA 1.1
Delay
0.0 s
100.0 s
5.0 s
4123
0(4)-20mA 1.1
Output A
R0 (none)
R26 (relay 26)
R0 (none)
4124
0(4)-20mA 1.1
Output B
R0 (none)
R26 (relay 26)
R0 (none)
4125
0(4)-20mA 1.1
Enable
OFF
ON
OFF
4126
0(4)-20mA 1.1
Fail class
See description of fail classes
4130 0-20 4-20mA 1.2
No.
Setting
Min. setting
Max. setting
Factory
setting
4131
0(4)-20mA 1.2
Set point
4mA
20mA
10mA
4132
0(4)-20mA 1.2
Delay
0.0 s
100.0 s
5.0 s
4133
0(4)-20mA 1.2
Output A
R0 (none)
R26 (relay 26)
R0 (none)
4134
0(4)-20mA 1.2
Output B
R0 (none)
R26 (relay 26)
R0 (none)
4135
0(4)-20mA 1.2
Enable
OFF
ON
OFF
4136
0(4)-20mA 1.2
Fail class
See description of fail classes
4250 0-20 4-20mA 2.1
No.
Setting
Min. setting
Max. setting
Factory
setting
4251
0(4)-20mA 2.1
Set point
4mA
20mA
10mA
4252
0(4)-20mA 2.1
Delay
0.0 s
100.0 s
5.0 s
4253
0(4)-20mA 2.1
Output A
R0 (none)
R26 (relay 26)
R0 (none)
4254
0(4)-20mA 2.1
Output B
R0 (none)
R26 (relay 26)
R0 (none)
4255
0(4)-20mA 2.1
Enable
OFF
ON
OFF
4256
0(4)-20mA 2.1
Fail class
See description of fail classes
4260 0-20 4-20mA 2.2
No.
Setting
Min. setting
Max. setting
Factory
setting
4261
0(4)-20mA 2.2
Set point
4mA
20mA
10mA
4262
0(4)-20mA 2.2
Delay
0.0 s
100.0 s
5.0 s
4263
0(4)-20mA 2.2
Output A
R0 (none)
R26 (relay 26)
R0 (none)
4264
0(4)-20mA 2.2
Output B
R0 (none)
R26 (relay 26)
R0 (none)
4265
0(4)-20mA 2.2
Enable
OFF
ON
OFF
4266
0(4)-20mA 2.2
Fail class
See description of fail classes
4-20mA inputs have wire break function. Wire break alarm will be active when
current goes below 2,5mA. It’s not possible to disable the wire break function.