MEC 310 GENSET CONTROLLER
PM075 REV 2 09/08/20
Page 56
THOMSON TECHNOLOGY
The TPS 300 software setting looks like this:
VDO input 3, cooling water temperature
VDO sensor
type
Temperature
Type 1
Type 2
Type 3
Type 4
°C
°F
Ω
Ω
Ω
Ω
40
104
291.5
480.7
69.3
Configurable
50
122
60
140
134.0
222.5
36.0
70
158
97.1
27.9
80
176
70.1
113.2
19.8
90
184
51.2
83.2
15.8
100
212
38.5
62.4
11.7
110
230
29.1
47.6
9.5
120
248
22.4
7.4
130
266
28.9
140
284
150
302
18.2
8 settings are available from 0-10 bar.
Type 4 is fully configurable with 8 points in the range 0-2500
Ω
and 40-150°C or
104-302°F.