MEC 310 GENSET CONTROLLER
PM075 REV 2 09/08/20
Page 40
THOMSON TECHNOLOGY
Function
Description
Inhibit 1
Inhibit 2
Inhibit 3
M-logic outputs: Conditions are programmed in M-logic
GB ON (TB ON)
The generator breaker is closed
GB OFF (TB ON)
The generator breaker is open
Run status
Running detected and the timer in menu 6160 expired
Not run status
Running not detected or the timer in menu 6160 not expired
Generator voltage >
30%
Generator voltage is above 30% of nominal
Generator voltage <
30%
Generator voltage is below 30% of nominal
MB ON
The mains breaker is closed
MB OFF
The mains breaker is open
Idle speed
Idle speed depends of the engine manufacture
Shutdown override
Inhibit if Shutdown override input is active
If an alarm is configured to activate a limit relay, the relay will activate despite the
fact that the inhibit input is ON.