Thomas & Betts RENZOR FT 30 Скачать руководство пользователя страница 9

Form RZ-NA-I-FT, Mfg No. 173473 Rev  8, Page 9

Roof or Building Overhang

3’ (1M) minimum

12”

(305mm)

minimum

6’ (2M)

minimum

Wall

Parapet or

Adjoining Building

Approved clearance

thimble for single-wall

vent pipe is required

when flue pipe extends

through combustible

materials.

Note position of vent

cap openings.

Pitch flue pipe down toward outlet

1/4” per foot for condensate drainage.

(NOTE: Applies to entire horizontal

vent run.)

Adjoining Building

Parapet or

Roof or Building Overhang

6’ (2M)

minimum

3’ (1M) minimum

12”

(305mm)

minimum

Wall

Approved clearance

thimble is required

when flue pipe extends

through combustible

materials. Follow

the requirements

 of the double-wall

 pipe manufacturer.

Pitch flue pipe down toward

outlet 1/4” per foot for con-

densate drainage.

(NOTE: Applies to entire

horizontal vent run.)

Note position of

vent cap openings.

6” (152mm) minimum

Follow instructions on page 8 to join single

and double-wall pipe and to seal the connection.

Figure 7B - Horizontal Vent Terminals

Horizontal Vent Terminal
Clearances

A vent cap is required. Maintain a clearance
of 12" (305mm) from the wall to the vent
terminal cap for stability under wind condi-
tions.

Products of combustion can cause discolora-
tion of some building finishes and deteriora-
tion of masonry materials. Applying a clear
silicone sealant that is normally used to pro-
tect concrete driveways can protect masonry
materials. If discoloration is an esthetic prob-
lem, relocate the vent or install a vertical vent.

Structure

Minimum Clearances for Vent Termination
Location (all directions unless specified)

Forced air inlet within 10 ft (3.1m)

3 ft (0.9m) above

Combustion air inlet of another appliance

6 ft (1.8m)

Door, window, or gravity air inlet

4 ft (1.2m) horizontally

(any building opening)

4 ft (1.2m) below
1 ft (30cm) above

Electric meter, gas meter * and relief

4 ft (1.2m) horizontally

equipment
Gas regulator *

3 ft (0.9m)

Adjoining building or parapet

6 ft (1.8m)

Adjacent public walkways

7 ft (2.1m) above

Grade (ground level)

7 ft (2.1m) above

*Do not terminate the vent directly above a gas meter or service regulator.

Single-Wall Vent Run
and Single-Wall
Terminal End

Single-Wall Vent Run and Double-Wall Terminal End

12. Gas Piping and Pressures

WARNING: This appliance is equipped for a
maximum gas supply pressure of 1/2 pound, 8
ounces, or 14 inches water column. Supply
pressure higher than 1/2 pound requires
installation of an additional lockup-type service
regulator external to the unit.

PRESSURE TESTING SUPPLY PIPING

Test Pressures Above 1/2 PSI:

 Disconnect the heater and manual

valve from the gas supply line which is to be tested. Cap or plug the
supply line.

Test Pressures Below 1/2 PSI: 

Before testing, close the manual valve

on the heater.

All piping must be in accordance with requirements outlined in the
National Fuel Gas Code ANSI/Z223.1a (latest edition) or CAN/CGA-
B149.1 and B149.2 (See Paragraph 1). Gas supply piping installation
should conform with good practice and with local codes. Support gas
piping with pipe hangers, metal strapping, or other suitable material;
do no rely on the heater to support the gas pipe.

Unit heaters are orificed for operation with natural gas having a heat-
ing value of 1000 (± 50) BTUH per cubic ft or propane gas with a
heating value of 2550 BTUH per cubic ft. If the gas at the installation
does not meet these specifications, consult the factory for proper ori-
ficing.

Pipe joint compounds (pipe dope) shall be resistant to the action of
liquefied petroleum gas or any other chemical constituents of the
gas being supplied.

Install a ground joint union and manual shut-off valve upstream of the
unit control system, as shown in Figure 8. The 1/8" plugged tapping in
the shutoff valve provides connection for a supply line pressure test
gauge. The National Fuel Gas Code requires the installation of a trap
with a minimum 3" drip leg. Local codes may require a minimum drip
leg longer than 3" (typically 6").

Gas connection is 1/2" for Sizes 30-200 and 3/4" for Sizes 250-300.
Leak-test all connections by brushing on a leak-detecting solution.

WARNING: All components of a gas supply system
must be leak tested prior to placing equipment in
service. NEVER TEST FOR LEAKS WITH AN
OPEN FLAME. Failure to comply could result in
personal injury, property damage or death.

Содержание RENZOR FT 30

Страница 1: ...Follow the gas supplier s instructions If you cannot reach your gas sup plier call your fire department WARNING Improper installation adjustment alteration service or maintenance can cause property da...

Страница 2: ...be protected from damage by aircraft or other objects such as cranes and movable scaffolding In addition the heat ers must be located so as to be accessible for servicing adjustment etc 2 Warranty Re...

Страница 3: ...100 square inches free area for each opening See 1 in Figure 2 2 Air from outside through duct openings 1 square inch free area per 2000 BTUH See 2 in Figure 2 3 Air direct from outside openings 1 squ...

Страница 4: ...2 pt suspension Follow the illustrated instructions in Figure 3B Sizes 30 45 60 and 75 may be suspended with an optional ceiling sus pension kit Refer to Figure 3C Step by step instructions are includ...

Страница 5: ...Composite drawings are not proportional for all sizes Field Wiring K 115V 60Hz 1Ph Connections L Thermostat Wires 24V Figure 4 Dimensions inches Size 30 45 60 75 100 125 150 200 250 300 A 28 5 8 28 5...

Страница 6: ...ure that the vent is sized properly for the heater being installed A properly sized vent system is required for safe operation of the heater An improperly sized vent system can cause unsafe conditions...

Страница 7: ...t system it is necessary to use 4 pipe only on a Size 30 and 5 pipe only on Sizes 45 and 60 Sizes 45 and 60 will require an increaser collar at the venter outlet The maximum horizontal vent length for...

Страница 8: ...blems or unsafe conditions See the illustrations in Figures 7A and 7B for requirements of vertical and horizontal vent termination The vent terminal pipe may be either single wall or double wall Type...

Страница 9: ...above a gas meter or service regulator Single Wall Vent Run and Single Wall Terminal End Single Wall Vent Run and Double Wall Terminal End 12 Gas Piping and Pressures WARNING This appliance is equippe...

Страница 10: ...to correct settings by turning the regulator screw IN clockwise to increase pressure Turn regulator screw OUT counterclockwise to decrease pressure Derating by Manifold Pressure Adjustment for High A...

Страница 11: ...Failed to Detect or Sustain Flame 3 Flashes Pressure Switch Open or Closed 4 Flashes High Limit or Flame Rollout Switch Open 5 Flashes Flame Sensed and Gas Valve Not Energized Steady On Internal Failu...

Страница 12: ...OPEN CIRCUIT TO HIGH LIMIT OR FLAME ROLLOUT TERMINAL 5 FLASHES FLAME SENSED AND GAS VALVE NOT ENERGIZED STEADY ON INTERNAL FAILURE MICRO CONTROLLER FAILURE SELF CHECK NOTES 1 THE FOLLOWING CONTROLS A...

Страница 13: ...al probe which is electrically iso lated from ground When the flame impinges on the flame sensing probe the flame acts as a conduction path to ground The flame rectifies and completes the DC circuit a...

Страница 14: ...r water Immediately call a qualified ser vice technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water Operating Instructions an...

Страница 15: ...dure 1 Seal any unused openings in the venting system 2 Inspect the venting system for proper size and horizontal pitch as required in the National Fuel Gas Code ANSI Z223 1 or CAN CGA B149 1and B149...

Страница 16: ...ulation Check the vent system for soundness Replace any parts that do not appear sound Check the wiring for any damaged wire Replace damaged wiring See Paragraph 13 for replacement wiring requirements...

Страница 17: ...ld cause fuel gas to spill out of the back of the burner tube Fuel gas spilling out of the back of the burner tube will cause gas odor inside the building and if not corrected could eventually cause a...

Страница 18: ...he front of the heater On Sizes 100 300 the limit control is accessible in the control compartment Sizes 250 and 300 have an auxiliary limit control To access the addi tional limit on Size 250 and 300...

Страница 19: ...unded f Make certain integrated circuit board is grounded to ignitor g Circuit board not grounded g Make certain integrated circuit board is grounded to furnace chassis h Faulty integrated circuit boa...

Страница 20: ..._____________________________ Unit Serial No __________________________________________ Date of Installation __________________________________________ PROBLEM PROBABLE CAUS E REMEDY No heat Heater 1...

Отзывы: